Desa RL2718PA/NA User Manual

Page of 40
www.desatech.com
113097-01E
7
 
Example:
 
Gas water heater 
  ____________ Btu/Hr
 
Vent-free fireplace  +  ___________ Btu/Hr
 
Total 
=  ___________ Btu/Hr
4.  Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.
 
 _________Btu/Hr (maximum the space can support) 
 
 _________Btu/Hr (actual amount of Btu/Hr used)
 
Example:
  51,200 Btu/Hr (maximum the space 
can support) 
 
 
79,000  Btu/Hr  (actual  amount  of 
Btu/Hr used)
The space in the example is a confined space because 
the actual Btu/Hr used is more than the maximum 
Btu/Hr the space can support. You must provide ad-
ditional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconfined 
space, remove door to adjoining room or add 
ventilation grills between rooms. See Ventilation 
Air From Inside Building.
B.  Vent room directly to the outdoors. See Ventila-
tion Air From Outdoors
.
C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 
size makes room unconfined. 
If the actual Btu/Hr used is less than the maximum 
Btu/Hr the space can support, the space is an un-
confined space. You will need no additional fresh 
air ventilation.
  WARNING:  If  the  area  in 
which the heater may be oper-
ated is smaller than that defined 
as an unconfined space or if the 
building  is  of  unusually  tight 
construction, provide adequate 
combustion and ventilation air 
by one of the methods described 
in the National Fuel Gas Code, 
ANSI Z223.1/NFPA 54 Section 5.3 
or applicable local codes. 
VENTILATION AIR
Ventilation Air From Inside Building 
This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining 
unconfined space, you must provide two perma-
nent openings: one within 12" of the ceiling and 
one within 12" of the floor on the wall connecting 
the two spaces (see options 1 and 2, Figure 2). You 
can also remove door into adjoining room (see 
option 3, Figure 2). Follow the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for 
Combustion and Ventilation for required size of 
ventilation grills or ducts. 
AIR FOR COMBUSTION 
AND VENTILATION
Continued
  40,000
  39,000
  79,000
Figure 3 - Ventilation Air from Outdoors
Figure 2 - Ventilation Air from Inside 
Building
Outlet
Air
Ventilated
Attic 
Outlet
Air
Inlet
Air
Inlet Air
Ventilated 
Crawl Space
To 
Crawl
Space
To Attic
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills 
Into Adjoining Room,
Option 2
Ventilation
Grills 
Into Adjoining 
Room,
Option 1
12"
12"
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or 
ducts. You must provide two permanent openings: 
one within 12" of the ceiling and one within 12" 
of the floor. Connect these items directly to the 
outdoors or spaces open to the outdoors. These 
spaces include attics and crawl spaces. Follow the 
National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
Section 5.3, Air for Combustion and Ventilation for 
required size of ventilation grills or ducts. 
IMPORTANT:
 Do not provide openings for inlet 
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the attic 
will activate the power vent.