Mitsubishi Electronics PUHY-P72 User Manual
[
VIII Test Run Mode ]
- 140 -
HWE08040
GB
Operation
Outdoor unit model
PUHY-P336TSHMU-A
PUHY-P96THMU-A
PUHY-
P120THMU-A
PUHY-
P120THMU-A
Operating
conditions
conditions
Ambient
tempera-
ture
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
unit
No. of connected
units
units
Unit
6
No. of units in opera-
tion
tion
6
Model
-
54/54/54/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
37 [82]
Outdoor
unit
unit
Electric current
A
82.2
Voltage
V
230
Compressor frequency
Hz
65
72
72
LEV open-
ing
ing
Indoor unit
Pulse
395/395/395/395/395/395
SC (LEV1)
171
171
171
LEV2
1400
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
pressure (before accumulator)
MPa
[psi]
2.89/0.88
2.89/0.88
2.89/0.88
[419/128]
[419/128]
[419/128]
Temp. of
each sec-
tion
each sec-
tion
Outdoor
unit
unit
Discharge (TH4)
°C [°F]
74 [165] 73 [163] 73 [163]
Heat exchanger out-
let
let
(TH3)
46 [115] 40 [104] 40 [104]
Accumulator
inlet
10 [50] 10 [50] 10 [50]
Accumulator
outlet
10 [50] 10 [50] 10 [50]
SCC outlet (TH6)
26 [79]
20 [68]
20 [68]
Compressor
inlet
14 [57] 15 [59] 15 [59]
Compressor shell
bottom
bottom
38 [100] 42 [108] 42 [108]
Indoor
unit
unit
LEV
inlet
25 [77] 19 [66] 19 [66]
Heat exchanger
outlet
outlet
10 [50] 10 [50] 10 [50]