Mitsubishi Electronics PKA-A30KA.TH User Manual

Page of 32
8. REMOVING THE HEAT EXCHANGER
(1) Remove the panel and the corner box. (Refer to 1.)
(2) Remove the electrical box (Refer to 3.) and the nozzle 
   assembly (Refer to 4.).
(3) Remove the water cut.
(4) Remove the pipe thermistors from each holder.
(5) Disconnect the connector for ground wire.
(6) Remove 3 screws fixing the left side of the heat 
   exchanger. (See Photo 9)
(7) Remove the heat exchanger.
9. REMOVING THE ROOM TEMPERATURE THERMISTOR
(1) Remove the panel and corner box. (Refer to 1.)
(2) Remove the electrical box covers.
(3) Remove the room temperature thermistor.
(4) Disconnect the connector (CN20) on the indoor controller
  
board.
Photo 11
Photo 12
Photo 13
Heat exchanger
Water Cut
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
C
Copyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Mar. 2009  No.OCH457 PDF 6
Made in Japan
New publication, effective Mar. 2009
Specifications subject to change without notice
Indoor controller
board (I.B.)
Room temp. 
thermistor (TH1)
Liquid pipe
thermistor (TH2)
Lead wire for TH5
Connector for 
ground
Heat exchanger
PHOTOS
OPERATION PROCEDURE