4.Functional specification 
4.1 Communication Protocol Specification 
 
  1) Protocol Outline 
BACnet/IP which applied to ANSI/ASHRAE 135-1995, 135a, 135b correspondingly on UDP/IP 
of Ethernet is used.   
 
 
 
APDU of BACnet
NPCIof BACnetNETWORK 
BVLL Header
UDP Header 
IP Header 
Ether Header 
 
  2) Ether Header 
A physical layer sets a transmission medium to 10 BASET by Ethernet. 
 
  3) IP Header 
The private address of Class C is recommended (*1).        Subnet mask 255.255.255.0 
*1: Recommendation value (range) [192.168.1.1]~[192.168.254.254] 
 
 
 
[192.168.0.0] and [192.168.255.255] do not use it. 
 
  4) UDP Header 
The default UDP port of a unicast and broadcasting is set to 47808 (OxBAC0). 
 
  5) BVLL Header 
BVLC type (one octet) 
0x81 fixation (BVLL to BACnet/IP) 
BVLC function (one octet)    0x0A At the time of a unicast 
0x0B At the time of broadcasting 
BVLC length (two octets)    Arbitrary (wording-of-a-telegram length setup: a big endian specification) 
 
    6)
 NPCI of BACnetNETWORK
 
Version (one octet)   
0x01 Fixation 
Control (one octet)        0x04 Those with a response message 
                                                        0x00 With no response message 
 
  7) APDU of BACnet 
It has arbitrary lengths of 1024 or less octets. Contents details are ANSI/ASHRAE135-1995, 135a, 135b   
references. 
 
  8)Application of BACnet 
The instance number of a Device object 
3(Setting change of a instance number is possible) 
Segmentation 
   Transmission 
and 
reception 
are 
un-supported. 
APDU which can be received 
 
1024 octet 
APDU timeout 
 
 
 
3 sec(Setting change of a instance number is possible) 
Vender 
ID    99 
Process ID 
 
 
 
blank (Setting change of a process ID is possible) 
 
 7