After completing the procedures described in "6 Installation Method" and "7 Wiring Method", set the initial settings in 
accordance with the procedure described below.  
(1) M-NET address settings
(2) Use the dip switches to select functions.
Select the function required for each input channel to be used.
The switch assignment for each channel is shown below. Configure each of the settings while referring to "9 Switch List".
(3) Turn on the power of this device.
Verify that the LED16 (CPU power on) and LED17 (M-NET power on) are lit. 
(4) Set the time.
Set the current time from a system controller (G(B)-50A or TG-2000A) or a Maintenance Tool. 
(5) Set the meter settings so that this device is a target for control from a system controller (G(B)-50A or TG-2000A). 
Configure the settings of the system controller (G(B)-50A or TG-2000A). For details, refer to the instruction manual for the G(B)-50A 
or TG-2000A.
*1: The pulse unit of the watt-hour meter being used should be 1 kWh/pulse or less. Note that the apportioning error will increase if a watt-hour meter with 
large pulse unit is used. 
*2: Values measured with this device cannot be used for the transaction and certification purposes mentioned in the Measurement Law.  
8
Initial Setting Procedure
SW06
SW07
Note: 
• An address from 01 to 50 can be set. 
• Set an address that is not the same as that of 
another unit.
The address is set to "01" at factory shipment.
In the case of address "41"
10s
1s
Setting
Operation Switch
Ch1
Ch2
Ch3
Ch4
Whether to use Input contact
SW01-1
SW01-2
SW01-3
SW01-4
Pulse weight value
SW02-1, 2
SW02-3, 4
SW02-5, 6
SW02-7, 8
Note:  Be sure to configure the pulse weight settings. If these setting are not configured, the charge function and peak cut control will 
not work normally because correct measurement of usage amounts will not be made.
Setting
Setting with G(B)-50A
Setting with TG-2000A
Pulse weight value
Set the pulse weight value setting switch (SW02) to the "SC setting", and set the setting with 
G(B)-50A or TG-2000A.
Unit for calculation
Set the volume unit (kWh, m
3
, MJ) with G(B)-50A or TG-2000A.
Period of time for calculation
Set the period of time for calculation of  the rates.
Time for calculation
Set the time for daily calculation.
Date for calculation
Set the date for monthly calculation.
Note: 
• Configure the settings of the TG-2000A connection system from TG-2000A.
If these setting are not configured, the charge function and peak cut control will not work normally because correct measurement 
of usage amounts will not be made.
• Be sure to set the pulse weight settings from this device or a system controller (G(B)-50A or TG-2000A). 
If these setting are not configured, the charge function and peak cut control will not work normally because correct measurement 
of usage amounts will not be made.