Honeywell 700 User Manual

Page of 40
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
15
66-2069—02
using key sequence below at the front panel of the 
700 as follows:
1.
Press and hold BNR-OFF SEQ START/END 
button for 2 seconds.
2.
Press up arrow to change setting from P0 to P1.
3.
Press STORE.
The factory default Modbus address of the 700ACSP and 
700DCSP is 0 and must be changed to a number between 1 
and 32 to establish communication between the signal 
processor and the host control. When more than one signal 
processor is in the network, ensure that each signal processor 
has a unique Modbus address within the range of 1 to 32.
Modbus RTU Function Supported
Four Modbus functions are supported:
• 01 Output coil read
• 03 Holding register read
• 06 Preset single holding register
• 16 Preset multiple holding register
NOTES:
Before Model 700 signal processors are 
connected to the RS-422 bus, their individual 
Modbus addresses must be set to differing values 
between 1 and 32.
The RESET button on front of the 700ACSP or 
700DCSP signal processors is used to set the 
Modbus address.
Press and hold the RESET button for two 
seconds and the current address will appear. It 
may be changed with the up or down arrow keys.
Pressing the STORE button will store the new 
address.
Table 4. MODBUS registers map.
Register
Name
Description
Minimum
Maximum
40001
FLAMECOUNT
Flame count of active viewing head (read only)
0
3425
40002
PROCSTATUS
Processor status bitmask (read only)
bit 1:    flame on relay status (1=relay energized, 0=off)
bit 2:    Processor Lockout status (0 =lockout, 1=not lockout)
bit 3:    Panel access disabled (1=disabled, 0=enabled)
bit 4:    4 - 20 ma output (0=0 to 20, 1=4 to 20)
0
255
40003
FLAMEON
Flame On setpoint (read/write)
3 (S70X)
29
40007
OUTPUTGAIN
Gain of the 0/4-20mA output (read/write)
20
80
40010
IRGAIN
IR sensor gain setting (read/write)
1
9
40012
UVTGAIN
UV tube gain setting (read/write)
1
9
40017
TYPE
Viewing head type bitmask (read only)
bit 0:    UV viewing head
bit 1:    IR viewing head
-
-
40021
TIMEDELAY
Time Delay (read only)
=1 for 700XXSP
1
2
40022
FFRT
Flame failure response time setting in seconds (read/write)
1
3
40023
VERSION
Firmware version (read only)
-
-
40024
MODEL
Model number (read only)
-
-
40084
ERRORCODE
Error code (read/write)
NOTE: writing a non zero number to this register is not allowed 
-
-
40085
BAUD
Baud rate setting (bits/second). Only affects RS-485 
communication, not IRDA. (read, write) 
96=9600 (default), 192=19200. 
The SP and the master device must have the same baud 
settings.
96
192
40086
PARITY
Parity setting. Only affects RS-485 communication, not IRDA. 
(read/write)
0= none (default), 1=odd
0
1
40087
ADDRESS
Modbus address used by RS-485 and IRDA (read/write).   
Each device must have a unique address.
0
247
40089
PROTOCOL
Protocol (read/write)
0=Honeywell protocol, 1=Modbus protocol
0
1