HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
66-2069—02
34
As an added safety feature, the coil of the Flame Relay is 
wired in series with a second pole of contacts on a Self Check 
Relay. The Self Check Relay is designed to be closed during 
normal operation of the signal processor and open during 
detection of a fault or power down. It is physically impossible 
for the Flame Relay to be closed if the Self Check Relay is 
open, unless the contacts of the Flame Relay are welded 
closed or the contacts of the Self Check Relay are welded 
closed. To reduce the chance of a false flame on condition, it 
is recommended that the user wire the Flame and Self Check 
Relays in series.
Also, as another added safety feature, neither relay can be 
driven by a simple continuously high or continuously low 
signal. Each relay must be driven by an alternating signal of 
the proper frequency and duty cycle from the processor.
700AC or 700DC Signal Processor 
Proof Test Interval
The Proof test must be conducted every 1 to 5 years. This 
range is given to allow for the test to be performed during the 
normally scheduled burner shutdown period. It is the 
responsibility of the user to perform the proof test in the 
specified time frame.
The following diagram presents the dependence of the 
PFD
AVG
 on the proof test interval. The PFD
AVG
 increases as 
the proof test interval increases.
Fig. 27. Dependence of the PFD
AVG
 on the proof test interval for 700AC.
 
Fig. 28. Dependence of the PFD
AVG
 on the proof test interval for 700DC.
0.00E
+00
5.00E
-05
1.00E
-04
1.50E
-04
2.00E
-04
2.50E
-04
3.00E
-04
3.50E
-04
4.00E
-04
0
                    
1
                    
2
                    
3
                     
4
                   
5
                    
6
                    
7
                    
8
                    
9
                   
10
TIME (YEARS)
PFD
 AVG
M35037
700 AC PFD
AVG
 VS TIME
0.00E
+00
5.00E
-05
1.00E
-04
1.50E
-04
2.00E
-04
2.50E
-04
3.00E
-04
3.50E
-04
4.00E
-04
0
                    
1
                    
2
                    
3
                     
4
                   
5
                    
6
                    
7
                    
8
                    
9
                   
10
TIME (YEARS)
PFD
 AVG
M35038
700 DC PFD
AVG
 VS TIME