Honeywell 700 User Manual

Page of 40
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
66-2069—02
6
Viewing Head Connector and Wiring
Viewing heads are wired to the appropriate terminals located 
on bottom of the 700ACSP, 700DCSP, P531 or P532 signal 
processors. The terminals are listed functionally in Table 2.
Connectors and cables are shown in Fig. 3, Fig. 4, and Fig. 5. 
Fig. 3 shows the viewing head cable with the 1/2 in. NPT pipe 
fitting and pigtail for use in a conduit. The PF model comes 
with 50 feet of Honeywell C330S cable. This cable is 
recommended for all new installations. It has ITC and CIC 
ratings for hazardous location. Figs. 4 and 5 describe the 
C330S cable used with the right angle field-wireable 
connector. Refer to “Accessories” on page 9 for part numbers.
The customer may also supply his own cable; a replacement 
mating viewing head connector should be ordered. Refer to 
 
The use of 22g, 4-
conductor cable with shield and drain is recommended. The 
shield should be foil and braid type surrounding all 
conductors. The shield should be connected to GND at the 
processor end. The cable diameter should not exceed 0.307" 
in order for it to go through the hex bushing in the connector. 
But note that wiring the cable to the connector is not easy 
because of the limited space. Also, the LED indicator 
assembly must be mounted inside the connector and, 
preferably, soldered in place. Thus, it is recommended to 
purchase a pre-wired cable and connector assembly from 
Honeywell.
NOTE: FOR CLASS I, DIV 2 RATING, CABLING IN 
HAZARDOUS LOCATIONS MUST COMPLY WITH 
NEC ARTICLE 500 REQUIREMENTS AND 
APPLICABLE GOVERNING CODES.
In the U.S., cables should have UL’s ITC rating; in Canada, 
cables should have CSA’s CIC rating. The recommended 
C330S cable has both ratings.
NOTE: To obtain a NEMA 4X seal between the connector 
and the viewing head, tighten the metal 
connector ring securely.
Fig. 3. Model 700 Viewing Head Cable With 1/2 in. NPT Fitting.
Table 2. Terminal Descriptions.
700ACSP or 
700DCSP 
Terminal
P531 or 
P532 
Terminal
Description
VH SIG
VH3 SIG
Flame Signal from Viewing Head
VH SC
VH3 SC
Shutter Drive Signal to Viewing 
Head
VH +V
VH3 +V
+24VDC Power to Viewing Head
VH GND
VH3 GND
GND Signal Ground
WHITE
BLACK
RED
GREEN
TERMINAL
VH SIG
VH SC
VH +V
VH GND
CONDUIT
ENCLOSURE
S702PF, S702HFPF OR S706PF
SHIELD
C330S YELLOW 4-CONDUCTOR
WITH DRAIN AND SHIELD
STANDARD "PIGTAIL" LENGTH = 10 FEET (3 METERS)
M34285B