Honeywell 700 User Manual

Page of 40
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
9
66-2069—02
position has been decided. A continuous flow of air must be 
maintained in order to reduce the conducted heat and to keep 
the sight pipe and viewing head lens free of dirt and debris. Air 
required is about 5 SCFM (0.13 Nm3 /min) delivered at 1 in. 
(25mm) above the maximum pressure as measured at the “Y” 
or “T” section of the purge air connection for each viewing 
head. The air supply must be clean, free of oils and water, and 
preferably cool. In order to electrically isolate the viewing 
head, the purge air line should be installed using an insulating 
material, such as a rubber hose, in between the purge air line 
and the viewing head.
Vibration
Do not install the viewing head where it could be subject to 
high vibration. Provide an anti-vibration mount if excessive 
vibrations are present.
Clearance
Make sure there will be sufficient room to remove the viewing 
head housing for servicing.
Viewing Head Mounting
Honeywell offers a range of swivel mounts, both pipe thread or 
flange mounting for use with sight pipes or direct wind box 
website for further details.
Viewing Head Sighting
The sighting of the viewing head should be parallel to the 
center line of the burner in the direction of the flame. If used, 
the sight pipe should be mounted as close to the center line 
as possible so as to sight along the flame rather than across 
the flame. Doing so will ensure continuous flame detection 
under changing load conditions. See Fig. 15, 16 and 17.
Utilizing a sighting or the sight pipe aimed at the root of the 
flame (where the turbulent combustion air mixes with the 
flame) is a good starting point for optimizing the sighting. 
Where practical, using a swivel mount to “zero-in” on the 
highest signal will assure maximum performance. The 
optimum scanner location is parallel to the burner center line. 
The use of a swivel mount allows for line of sight adjustment, 
where practical to use.
Examples of viewing head installation with and without a 
swivel mount are shown in Fig. 13 and Fig. 14. If using a sight 
pipe, its diameter should be large enough to allow a 
reasonable field of view, and to allow for adjustment of the 
swivel mount angle.
In some instances, it may be beneficial to use two sets of 
setpoints for Flame On, Flame Off and gain. The two-channel 
capability (primary and alternate viewing head settings) is 
ONLY possible when using the P531 or P532 signal 
processors; it is not possible when using the 700ACSP or 
700DCSP signal processors. The switch-over from Channel A 
to Channel B can be implemented from the burner control 
system. Refer to the P531/P532 user manual, 66-2068, for 
further information regarding switch-over and the use of 
Channels A and B with independent settings.
ACCESSORIES
Orifice disks (kit M-702-6) - Used to reduce the signal 
brightness in cases where the signal brightness is too strong. 
Located immediately in front of the lens, it will reduce the 
amount of signal to the sensor. Bag assembly contains orifice 
disks and retaining rings. Orifice disks come with 3/8, 1/4, 
3/16 and 1/8 inch diameter holes. Contact the factory for 
guidance in using orifice disks.
Insulating nipple (R-518-13) - 1/2-in. NPTM Ultem heat and 
electrical insulating nipple typically used in conjunction with a 
swivel mount and union.
VH insulating mounting block (700UA, 800UA) - 1/2 in. 
NPTF Ultem heat and electrical insulating mounting block, 
used in place of the supplied Delrin mounting block. 1/4 in. 
NPTF purge air connection. Typically used in conjunction with 
a swivel mount. Rated for continuous service up to 320°F 
(160°C).
Swivel mounts, small (700-1, 700-2, 700-3) - All have 1/2 in. 
NPTM viewing head connections on one end with varying 
process connections including 1 in. NPTF, 1/2 in. NPTF and 
1/2 in. flanged.
Swivel mounts, large (M-701-1, M-701-2, M-701-2-FLG, M-
701-2-SS, M-701-3, M-701-3P, M-701-4) - All have 1 in NPTF 
viewing head connections, one end with varying process 
connections including 2 in. pipe slip on, 2 in. NPTF, 2 in. 
flanged, 2 in. NPTF in stainless steel construction, 4.5 in. 
flanged with 3 bolts, 3 in. NPTF and 2-bolt flanged.   
Appropriate fittings must be used to adapt the 1/2 in. NPTF 
viewing head process connections.
Insulating locking coupler adapters (R-518-PT13, R-518-
PT13L) - 1/2 in. NPTM Ultem adapters insulate the viewing 
head electrically and thermally and are used with the R-518-
CL13-HTG locking couplers. The R-518-PT13L has a quartz 
lens.
Locking coupler (R-518-CL13-HTG) - Used with the R-518-
PT13 and R-518-PT13L insulating locking coupler adapters. 
Process connection end is 1/2 in. NPTF.
Connector - ASY786 --> Replacement field wireable
 
connector.
Cable and Connectors - S70X/S80X Viewing Heads 
ASY785 --> 50 foot C330S cable with pre-wired ASY786 
connector.
ASY785-200 --> 200 foot C330S cable with pre-wired ASY786 
connector.
Cable (C330S) - 4-conductor with drain, foil/braided shield. 
Sold per foot. 
Isolation Units (ISO-UNIT, ISO-UNITSS, ISO-UNITHPGT) - 
All have 1 in. NPTF connections with 1/2 in. NPTF purge ports 
and quartz window. Painted aluminum or stainless steel 
construction. The HPGT version has a 1/2 in. thick quartz 
window for higher pressures. Appropriate fittings must be 
used to adapt the 1/2 in. NPTF viewing head process 
connections.
Air cooling canister (700ACC, 800ACC) - Has an air inlet 
port on side. Used with vortex coolers. S80X models can be 
used with the 700ACC if the 800ACC-RING adapter is used.