Mitsubishi Electronics G-50A User Manual

Page of 31
2 Setting the Operating Environment   
Given below is an explanation of the PC settings and web browser settings that are required for using a web 
browser to monitor air conditioner units and perform operations. 
 
2-1 Setting the PC IP Address 
You need to set an IP address on the PC that will enable you to connect to the G-50A using a web browser. 
For instance, if the G-50A IP address is [192.168.1.1], the PC IP address will need to belong to the same 
system (for example [192.168.1.101]). 
If the G-50A is connected to an existing LAN, ask the LAN administrator to decide what PC IP address to use. 
Note: When using a G-50A dedicated LAN, we recommend the G-50A main unit be given an IP address within the 
range [192.168.1.1] — [192.168.1.40] and the PCs that will be connected to the G-50A be given an IP 
address within the range [192.168.1.101] — [192.168.1.150] 
 
(1) Click on [Control Panel] under [Start] to open the Control Panel. 
 
 
 
 
 
(2) In the Control Panel window, double click [Network and Dial-up 
Connections] and the Network and Dial-up Connections window will 
open. Double click on [Local Area Setting] and the [Local Area 
Connection Status] dialog will open. Click [Properties]. 
 
 
 
 
 
 
 
 
(3) In the [Local Area Connection Properties] dialog, click [Internet 
Protocol] to select it and click the [Properties] button.