Outdoor unit
6.Purging Method:To use vacuum pump
7
3-way valve
2-way valve
6.35mm(1/4")
12.7mm(1/2")
Push the air out of the indoor unit
and piping as followes:
(1) Remove the valve cap on 2-way
      valve in outdoor unit.
(2) Loosen by 1/2 turn the flare nut of
     gas pipe, which is conneted to
     3-way valve.
(3) Loosen 2-way valve by 90
o
 using
     hexagon wrench, and after approx.
     10 sec tighten it up. Gas comes out
     through flare nut on wide pipe. If no
     gas is discharged, tighten flare nut
     with specified torque.
(4) Open 2-way and 3-way valves
      using specified torque.
(5) Tighten the caps on the valves
      with specified torque.
Valve rod
Valve cap
7-9
20-25
Tighten torque N.m
When connecting pipe exceeds 5 meters, 20g refrigerant shall be added
per exceeding meter. Charge according to the following list.
Piping length
Additional amount
5m
7m
10m
No need
40g
During this procedure, 50g refrigerant will be discharged in piping.
(This must be strictly controlled within 90
o
 and 10 sec.)
Brand new outdoor unit is charged 50g more refrigerant than regulated weight.
Only for first installation, this extra 50g can be used to purge air in pipes.
Note: When extending piping, air inside piping shall be removed by using external
         refrigerant gas, charge according to the following list.
100g
HSU-12CR03-Y
HSU-18CR03-Y