Mitsubishi P288T(Y)SJMU-A PUHY-P312 User Manual

Page of 334
IX  Troubleshooting ]
- 264 -
HWE09120
GB
Items to be checked
Phenomena
Remedy
[4]
Check whether 
the inverter is 
damaged.
(During com-
pressor opera-
tion)
Put the outdoor unit into oper-
ation.
Check the inverter output volt-
age after the inverter output 
frequency has stabilized.
1)
Overcurrent-related problems oc-
cur immediately after compressor 
startup.
Error code : 4250
Detail code : 101, 106, 107
a. Check items [1] through 
[3] for problems.
b. Check that high and low 
pressures are balanced.
c.
Check that no liquid refrig-
erant is present in the 
compressor.
Go to "d." when the 
problem persists after 
compressor startup was 
repeated several times.
If normal operation is re-
stored, check the belt 
heater for problems.
d. Check that there is a pres-
sure difference between 
high and low pressures af-
ter compressor startup.
Check the high pressure 
with LED monitor for 
changes.
Replace the compressor if 
there is no pressure differ-
ence. (the compressor 
may be locked.)
2)
There is a voltage imbalance be-
tween the wires after the inverter 
output voltage is stabilized. 
Greater than the larger of the fol-
lowing values: imbalance of 5% or 
5V 
Replace the INV board if there 
is a voltage imbalance.
Check the belt heater for prob-
lems if there is no voltage im-
balance.
When the error occurred, 
liquid refrigerant may have 
been present in the compres-
sor.
[5]
Check the fan 
motor ground 
fault or the 
winding.
Remove the wire for the out-
door fan motor, and check the 
fan motor megger and the 
winding resistance.
1)
Fan motor megger failure 
Failure when the megger is 1Mohm 
or less.
Replace the fan motor.
2)
Fan motor disconnection 
Standard: The winding resistance 
is approximately several ohm.
(It varies depending on the temper-
ature, or while the inner thermo is 
operating, it will be 
 ohm)
[6]
Check the FAN  
board failure.
(1)
Check the fan output wir-
ing.
Connector contact failure
ŒBoard side (CNINV)
ŒFan motor side
Connect the connector.
(2)
Check the connector CN-
VDC connection.
Cnnector contact failure
Connect the connector.
(3)
Check the FAN board 
failure.
1)
The voltage imbalance among 
each motor wiring during operation
(The voltage imbalance is greater 
than the larger of the values repre-
sented by 5% or 5 V.)
Replace the FAN board.
2)
The same error occurs even after 
the operation is restarted.
                                    [YJMU-A]