MASTER LOCK B100 User Manual

Page of 32
100743
14
Air Output, Air Intake,
and Lint Filters
1. Remove upper shell (see
page 10).
2. Remove filter end cover
screws using 5/16" nut-
driver.
3. Remove filter end cover.
4. Replace air output and lint
filters.
5. Wash or replace air intake
filter (see Preventative
Maintenance Schedule,
page 8).
6. Replace filter end cover.
7. Replace fan guard and
upper shell.
IMPORTANT:
 Do not oil
filters
Air Intake Filter
Lint Filter
Filter End
Cover
Air Output
Filter
Fan Guard
Figure 20 - Air Output, Air Intake, and Lint Filters,
30/70,000 BTU/Hr Models
Air Intake Filter
Filter End
Cover
Lint Filter
Air Output
Filter
Figure 21 - Air Output, Air Intake, and Lint Filters,
90/150,000 BTU/Hr Models
PRESSURE GAUGE PLUG
PFA/OV 006B
Figure 22 - Pressure Gauge Plug Removal
Pressure
Gauge
Plug
Pressure
Gauge
Figure 23 - Adjusting Pump Pressure
Pump
Model
Pressure
30,000 BTU/Hr
2.6 PSI
70,000 BTU/Hr
3.8 PSI
90,000 BTU/Hr
4.4 PSI
150,000 BTU/Hr
4.9 PSI
(30/70,000 BTU/Hr Models Shown)
Relief
Valve
Fan Guard
(90,000 BTU/Hr
Model Shown)
Pump Pressure
Adjustment
1. Remove pressure gauge
plug from filter end cover.
2. Install accessory pressure
gauge (part number
HA1180).
3. Start heater (see Operation,
page 7). Allow motor to
reach full speed.
4. Adjust pressure. Turn relief
valve to right to increase
pressure. Turn relief valve
to left to decrease pressure.
See specifications at right
for correct pressure for
each model.
5. Remove pressure gauge.
Replace pressure gauge
plug in filter end cover.