Lg Electronics RVL469 User Manual

Page of 8
Siemens Building Technologies
CE1N2527E / 04.03.1999
Landis & Staefa Division
1/8
2
527
Heating Controller
Series B
RVL469
for use with a partner unit
 
Multifunctional heating controller for use in residential and non-residential
buildings; suitable for weather-dependent flow temperature control of heating
zones with or without room temperature compensation
 
For exclusive use on the bus together with an RVL47... heatinmg controller as
a partner unit
 
1 programmed plant type: three-position control of the mixing valve in a heat-
ing zone
 
Analog or digital setting of the heating curve, analog room temperature read-
justment, operating line principle for all other parameters
 
Operating voltage AC 230 V, CE conformity
  Types of buildings:
– Multi-family houses
– Single-family houses
–  Smaller non-residential buildings
  Types of plants:
–  Combined plants consisting of several heating zones and heat generation
  Types of heating systems:
–  Radiator, convector, underfloor and ceiling heating systems, radiating panels
Weather-dependent flow temperature control through control of the mixing valve in a
heating zone in combined plants.
Automatic mode
Automatic changeover from normal to reduced temperature, and vice versa,
according to the seven-day program, automatic changeover to holiday mode,
demand-dependent control of heating system (ECO function)
Setback mode
Continuous heating to the reduced temperature, with ECO function
Comfort mode
Continuous heating to the normal temperature, no ECO function
Standby
Frost protection is ensured in all operating modes.
The controller can be switched to manual operation.
Use
Functions
Heating zone control
Operating modes