Installation
1. Using  template  provided,  determine  mounting  loca-
tion.
2. Drill holes and attach mounting hardware (not includ-
ed).
IMPORTANT: THE HARDWARE AND THE SUPPORT-
ING STRUCTURE MUST BE CAPABLE OF SUPPORT-
ING A MINIMUM 150 LB. LOAD.
NOTE: All installation should be done to meet local
building code.
3. Mount cabinet on wall and securely tighten hardware.
4. Replace  motor/blower  assembly  in  cabinet.  Secure
two  wing  nuts  on  blower  base.  Reconnect  motor
electric cord plug assembly & heater plug.
5. Replace  intake  grille  with  louvers  facing  down  and
refasten knurled nuts.
FIELD POWER WIRING
WARNING:
ALL AIR CURTAINS SHOULD BE
INSTALLED BY QUALIFIED PERSONNEL.
1. Before  wiring  be  sure  that  available  power  supply,
voltage,  phase  and  frequency  corresponds  to  that
specified  on  heater  rating  plate.  In  addition,  make
certain that service capacity is sufficient to handle load
imposed by the equipment.
2. Install  all  wiring,  protection  and  grounding  in  accor-
dance  with  the  National  Electrical  Code  (NEC)  and
all local requirements.
WARNING: THIS FAN HAS AN INTERNAL SELF
RESETTING THERMAL  OVERLOAD  PROTECTOR.
ALWAYS DISCONNECT FROM POWER SUPPLY
BEFORE SERVICING.
3. Run proper size copper power supply conductors from
the  field  power  supply  disconnects,  (supplied  by
others) with insulation rated minimum 75°C (167.0°F).
One set of conductors from 208VAC, 50/60Hz supply
source  shall  be  routed  through  the  3/4  inch  conduit
knockout, using a suitable knockout connected to the
contactor contact terminals marked L1, L2, L3.
4. The  heater  control  box  must  have  an  unbroken
electrical  ground  to  minimize  personal  injury  if  an
electrical fault should occur.
FIELD CONTROL WIRING
Electric heater is equipped with a step-down transformer
for  24V  control  circuit. Thermostat  model  number  RSV-
130-R-54 must be used to energize heater with the fan
motor.  Connect  thermostat  wiring  from  thermostat  to
control leads in heated air curtain control box by means
of conduit or equivalent. A 1/2 inch knockout is provided.
Class 1 wiring is required.
5. Replace heater control box cover.
6. Unit is ready for operation.
7. Restore power.
NOTE: Air curtain has high/low selector switch. See
Operation section for proper setting instructions.
8. Upon  completion  of  all  installation,  inspect  unit  for
excessive  vibration  during  operation.  If  excessive
vibration  is  noticeable,  disconnect  power  supply.
Inspect 
mounting 
installation 
and 
refer 
to
Troubleshooting Chart for probable cause.
3
Figure 5 - Wiring Diagram
BU
COLOR CODE
RE - RED
WH - WHITE
BK/RD - BLACK W/ RED TRACER
YE - YELLOW
OR - ORANGE
BU - BLUE
LEGEND
HR - HEAT RELAY
TB - TERMINAL BLOCK
TR TRANSFORMER
PL - PILOT LIGHT
FL - FUSE LINK
HE - HEAT ELEMENT
HEATER SECTION
FIELD WIRING TO THERMOSTAT
THERMOSTAT
TERMINAL MARKING
TO POWER 
SUPPLY
PLUG
TB
L1
L2
L3
GR