Millennium Enterprises Z42 User Manual

Page of 92
882108-YIM-B-1012
Johnson Controls Unitary Products
53
TABLE 33: COMPONENT STATIC RESISTANCE
1, 2
COMPONENT COIL 
LOSSES
CFM
4,000
6,000
8,000
10,000
12,000
14,000
16,000
18,000
COIL LOSSES 25T
3 Row, 16 FPI, dry
-0.14
-0.18
-0.24
-0.34
-0.45
-
-
-
3 Row, 16 FPI, wet
Baseline
Baseline
Baseline
Baseline
Baseline
-
-
-
COIL LOSSES 30T
4 Row, 16 FPI, dry
-0.18
-0.22
-0.32
-0.45
-0.60
-0.76
-
-
4 Row, 16 FPI, wet
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
-
-
COIL LOSSES 40T
4 Row, 16 FPI, dry
-0.15
-0.22
-0.26
-0.31
-0.42
-0.53
-.0.65
-0.79
4 Row, 16 FPI, wet
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
FILTER LOSSES
2” TA or HI EFF.
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Rigid 6”, 65%
0.06
0.12
0.19
0.27
0.36
0.46
0.58
0.70
Rigid 6”, 95%
0.13
0.26
0.41
0.60
0.81
1.04
1.29
1.57
IGV LOSSES
25 & 30 Ton F.C.
0.02
0.05
0.08
0.13
0.19
0.26
0.34
0.43
40 Ton F.C.
0.01
0.03
0.05
0.08
0.11
0.15
0.19
0.25
GAS HEAT
267 MBH Heat
0.07
0.11
0.14
0.18
0.21
0.25
0.28
0.32
533 MBH Heat
0.14
0.21
0.28
0.35
0.42
0.49
0.57
0.64
800 MBH Heat
0.21
0.32
0.42
0.53
0.64
0.74
0.85
0.95
ELECTRIC HEAT
40KW
0.01
0.02
0.04
0.06
0.10
0.20
0.31
0.40
80KW
0.01
0.04
0.08
0.13
0.20
0.31
0.44
0.56
108KW
0.02
0.05
0.10
0.15
0.31
0.43
0.53
0.68
ECONOMIZER
0.03
0.06
0.10
0.15
0.21
0.28
0.35
0.43
POWER EXHAUST
0.02
0.05
0.08
0.13
0.18
0.25
0.32
0.41
1.
Baseline losses based on system/cabinet effects, wet standard coil and 2” throwaway filters at 70°F, 0 feet elevation with standard air.