advaNCEd CONfiguraTiON
Table 5. Advanced Configuration.
Menu Name
Menu Title (LCD 
top line)
Menu Options (LCD bottom 
line; defaults in bold)
Menu option description
Notes:
Heat Fan
HEAT FAN 
CONTROL
[HVAC] PANEL
Fan control by HVAC
In heat mode, fan controlled by HVAC or turned 
on by panel in call for heat.
 HVAC [PANEL]
Fan control by Panel
Stage 2 Timer
STAGE 2 TIMER
     [5 MIN]   > – <   [60 MIN]  
     [5 MIN]   >
5 minutes–60 minutes
Number of minutes to delay before engaging 
second stage.
Purge Timer
PURGE TIME
[2] 3.5  5  MIN
2.0 minutes
Number of minutes panel will purge following 
call for heat or cool.
 2 [3.5]  5  MIN
3.5 minutes
 2  3.5  [5] MIN
5.0 minutes
Purge Fan
FAN IN PURGE
[HVAC] PANEL
Fan control by HVAC
Fan controlled by HVAC or panel during purge.
 HVAC [PANEL]
Fan control by Panel
Purge Dampers
PURGE DAMPERS [UNCHANGD] OPEN
Dampers Unchanged
Damper position unchanged or all dampers 
open during purge.
 UNCHANGD [OPEN]
Dampers All Open
Auto Changeover Delay  CHANGEOVER 
DELAY
[15] 20  30  MIN
15 minutes auto changeover timer
Number of minutes to delay auto changeover 
when one zone is calling for heat and another 
is calling for cooling.
 15 [20] 30  MIN
20 minutes auto changeover timer
 15  20 [30] MIN
30 minutes auto changeover timer
DATS Enabled
DISCHARGE 
SENSOR
[NO] YES
Disabled
Enables or disables DATS. If Disabled, the 
Multistage DATS Inhibit setting is Disabled.
 NO [YES]
Enabled
DATS High Limit
DAT HIGH LIMIT
    [110 F]    > – <   [180 F]     
<   [160 F]    >
110 deg F–180 deg F
High temperature limit.
DATS Low Limit
DAT LOW LIMIT
     [30 F]    > – <    [60 F]     
<    [40 F]    >
30 deg F–60 deg F
Low temperature limit.
OT Temp Enabled
OT SENSOR
[NO] YES
Disabled
Enables or disables outdoor temperature 
sensor. If Disabled, the Multistage OT Temp 
Lockout setting is Disabled.
 NO [YES]
Enabled
OT Trip Point for 
Multistage Lockout
OT LOCKOUT 
TEMP
      [0 F]    > – <    [50 F]    
<    [50 F]    >
0 deg F–50 deg F
Above this temperature 2nd stage heat is 
locked out.
Multistage DATS Inhibit DAT MSTG INHIBIT NO [YES]
Enabled
Allow panel to downstage multistage equip-
ment when near DATS high or low limit.
 [NO] YES
Disabled
LCD Contrast Adjust
LCD CONTRAST
     [1]     > – <    [10]    
<   [5]     >
Contrast value 1–10
Sets LCD display contrast for ease of viewing. 
Lowest contrast is 1, highest contrast is 10.
Save Changes
SAVE CHANGES?
[NO] YES
Disabled
Saves or rejects the configuration settings.
 NO [YES]
Enabled
Reload Defaults
RELOAD 
DEFAULTS?
[NO] YES
Disabled
Restores the panel's default configuration 
settings.
 NO [YES]
Enabled
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 7 
for instructions on using these buttons.
Press the Mode button until the Wireless LED lights 
up. The TrueZONE must be configured for wireless 
devices to select Wireless mode.
4
CONNECT WirElEss dEviCEs
HOME
MODE
BACK
NEXT
CONFIG
CHECK OUT
ADJUST SETTING
M28194
WIRELESS
Press Next to add devices.
While the display alternates the Press Connect and 
Exit screens, push the Connect button(s) on the wire-
less device(s).
-OR-
Follow the instructions that came with the wireless 
device(s).
Press Next to exit.
Fig. 15