Honeywell HZ322 User Manual

Page of 12
HZ322 TrueZONE
 
69-299—0
spECifiCaTiONs aNd aCCEssOriEs
Input Ratings:
Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA 
or more.
Current Draw:
Zone Panel: 7.5 VA max.
All VA specifications at 24 VAC.
Wiring:
18- or 20-gauge solid (not stranded) wire.
Humidity Ratings:
5% to 90% RH non-condensing.
Temperature Ratings:
Shipping: -20° to 150°F (-29° to 66°C)
Operating: -40° to 165°F (-40° to 74°C)
Dimensions:
See below.
Emissions:
Complies with FCC Class B, part 15 requirements.
Fig. 1. HZ322 TrueZONE panel dimensions in 
in. (mm).
Table 1. Recommended Thermostats.
System Non-
Programmable
Programmable
Single-
Stage
TH5110D, TH3110D, 
T87N
TH8110U, TH6110D, 
TH4110D
Multi-
Stage
TH5220D
TH8320U, TH8321U, 
TH6220D, YTH9421C
Heat-
Pump
TH5220D (2H/1C 
only) 
TH3210D (2H/1C 
only)
TH8320U 
TH8321U 
TH6220D (2H/1C only) 
TH4210D (2H/1C only) 
YTH9421C
Wire-
less*
TH5320R
TH6320R
Note: All versions of the model numbers listed above 
will work with the applications they're listed for.
* Wireless adapter also required.
Table 2. Recommended Dampers.
Type
Honeywell 
Damper
Round Rectangular
Zone
Spring-open/
power-closed
ARD
ZD
Zone
Power-open/
power-closed
MARD/
RRD
For recommended 
dampers call the 
Honeywell Zoning 
Hotline at 
1-800-828-8367.
Bypass Static pres-
sure regulat-
ing damper
SPRD/
MARD
SPRD
Table 3. Maximum Dampers.*
Ambient Temp. Maximum Damper VA per Zone
100°F (38°C)
28.8
160°F (71°C)
16.8
* Use an SDCR (Slave Damper Control Relay) for addi-
tional dampers.
  Maximum dampers per panel is limited by transformer 
size.
  Ensure transformer is large enough to power the panel 
(10 VA) and dampers.
Table 4. Accessories.
Accessory
Description
40 VA transformer*
AT140A1042*
75 VA transformer
AT175A1008
Discharge Air 
Temperature Sensor *
DATS C7735A1000*
Wireless Outdoor Air 
Temperature Sensor
C7089R1013
Wireless Adapter
THM4000R1000
SDCR
Slave Damper Control 
Relay
* Included in HZ322K kit.
M28011
1.86 (47)
8 (203)
11.5
(292)