Troubleshooting
27
8.0
T
ROUBLESHOOTING
Table 14
Troubleshooting guide
Problem
Probable Cause
Remedy
Unit will not start
No power to unit
Check voltage to input circuit breaker.
Control voltage circuit 
breaker open
Locate short and reset breaker.
Shut off by external 
thermostat or stat is 
defective
Check operation of thermostat.
No cooling
Low refrigerant 
charge
Check with gauges.
Compressor contactor 
not pulling in
Check voltage at contactor. If not present refer to print and determine 
voltage loss. Check enthalpy sensor for full CCW or D setting.
No output from 
thermostat
Check operation of stat. Should have voltage output to Y terminal during 
cooling.
Unit cycles on
high pressure switch
Loss or restriction of 
air flow
Check condenser blower assembly for proper operation. Check for dirty 
coil or inlet grille restriction.
Defective fan cycling 
control
Switch should make @ 240 PSIG 
±10 (1655 kPa ±68.9). (Check settings 
on adjustable switch when supplied.)
Heat does not operate
No voltage output 
from thermostat
Check stat for proper output to W terminal.
Fuseable link blown
Check for open and replace.
Bad contactor
Check for open and replace.