Siemens 125-3208 User Manual

Page of 64
SED2 VFD Electronic Bypass Option Operating Instructions 
36 
 
Siemens Building Technologies, Inc. 
 
Parameter Description 
Action 
Setting/ 
Default 
P1213 
Restart Time Increment 
Selects the amount (seconds) 
that the restart time is 
incremented for each restart of 
the SED2 if P1210 automatic 
restart is activated.  
1. Press   to enter the SED2 
parameter mode and to display 
r0000
.  
2. Press   to advance to 
parameter P1213.  
3. Press   to access the 
parameter values level. 
4. Press   to advance to 
desired value.  
5. Press   to confirm and save 
the setting. 
Minimum = 0 
Default = 30 
Maximum = 
1000 
Suggested = 
10 
 
Vdc Controller 
Parameter Description 
Action 
Setting/ 
Default 
P1240 
Configuration of Vdc 
Controller 
Enables/disabled Vdc controller.  
The Vdc controller dynamically 
controls the DC link voltage to 
prevent overvoltage trips on high 
inertia systems.  
Vdc-max automatically increases 
ramp-down times to keep the DC 
link voltage (r0026) within limits.   
0 = Vdc controller disabled 
1 = Vdc-max controller enabled 
2 = Reserved 
3 = Reserved 
1. Press   to enter the SED2 
parameter mode and to display 
r0000
.  
2. Press   to advance to 
parameter P1240.  
3. Press   to access the 
parameter values level. 
4. Press   to advance to 
desired value.  
5. Press   to confirm and save 
the setting. 
Minimum = 0 
Default = 1 
Maximum = 3