Required SED2 Parameter Settings 
Siemens Building Technologies, Inc. 
 
41 
Required SED2 Parameter Settings 
The following SED2 parameters are programmed by the factory before shipping. If 
these parameters are changed or if the SED2 is ever reset to factory default, you 
must reset these parameters as follows: 
Parameter Setting 
P0748 
P0702 in000 
P0702 in001 
P0731 52.3 
NOTES: 
1.  The Interlock Start on the Controller board is simply a follower that can be used 
to tell the drive to do anything by closing the SED2 Interlock Start and 
programming P0704. 
2.  The Programmable Output on the Controller board is simply a follower of the 
SED2 Relay.  
3.  The SED2 Fault must always be programmed as a fault. Do not change the 
SED2 relay fault for other uses via P0731.  
4.  Changing P0700 resets all digital inputs and P0702 will require programming.