INSTALLATION INSTRUCTIONS
TROL KIT
A.  If your installation included the optional electric heat kit,  
 
install it at this time. Follow the instructions with the  
 
 
heat package for its installation procedure.
B.  Terminate the 4-conductor control cable(s) protruding   
 
into the 4-/4” x 4-/4” (±/8”) roof opening. The  
 
 
cable(s) must be terminated with an RJ--4C-6P telephone  
 
 
connector. Refer to the crimp tool manufacture for    
 
crimping instructions.
Important:
 RJ-11-4C-6P connectors must be installed as shown 
in FIg. 4A.
C.  Remove the junction box cover from the Electronic    
 
Control Kit. See FIG. .
D.  Plug the electrical conduit (6-pin connector) from the    
 
upper unit into the mating connector in Electronic Con-  
trol Kit. See FIG. .
E.  Plug the control cable(s) into the telephone jack(s) on   
 
the Electronic Control Kit.  (It does not matter which  
 
 
one.)
F.  Route the Remote Temperature Sensor cable, if appli-  
 
cable, through the same round grommet where freeze  
 
 
control wires go into the Electronic Box. See FIG. .  
 
 
Connect it to the connector that matches its color.
g.  Insert the Freeze Control Sensor approximately ” into  
 
the evaporator coil fins as shown in FIG. 12.
H.  Locate the electronic control kit on the ceiling template  
 
as shown in FIG. 3. Drive two (2) #0 x 3/8” blunt point    
phillips head screws (provided) through ceiling template    
into holes in electronic control kit to hold it in place.
8.  WIRINg OF SySTEM
A.  CONNECTION OF LOW VOLTAgE WIRES
Disconnect the positive (+) 12 volt DC terminal at the 
supply battery.  Damage to equipment could occur if 
the 12 volt DC is not shut off.
 
 
.  Connect the previously run 2 VDC to the red and   
 
black wires protruding from the Electronic Control Kit.  
 
 
(In multiple zone installations, this needs to be done  
 
 
at only one zone.) Connect +2 VDC to the red wire;  
 
 
-2 VDC to the black wire.
 
2.  Connect the previously run furnace thermostat wires  
 
 
(if applicable) to the blue wires protruding from the    
 
electronic Control Kit. The polarity of these connec- 
 
 
tions does not matter.  If not used, terminate wire with  
 
 
twist connector.
 
3.  Connect the previously run Energy Management    
 
System wires (if applicable) to the yellow wires    
 
protruding from the Electronic Control Kit. The    
 
polarity of these    connections does not matter.  If not    
 
used, terminate   wire with twist connector. 
   