Goodman Mfg SS-CPH90-150 User Manual

Page of 36
P
roduCt
 S
PeCifiCationS
P
roduCt
 S
PeCifiCationS
6 www.goodmanmfg.com 
SS-CPH90-150
P
roduCt
 S
PeCifiCationS
 — 12½ t
onS
CPH150XXX
3BXXX
CPH150XXX
4BXXX
CPH150XXX
7BXXX
Cooling Capacity
Total, BTU/h
146,000
146,000
146,000
Sensible BTU/h
102,200
102,200
102,200
EER / IPLV
10.8 / 11.2
10.8 / 11.2
10.8 / 11.2
Decibels
83
83
83
ARI Reference #s
3554114
3554114
3554114
Heating Capacity
BTU/hr (47°F)
150,000
150,000
150,000
COP (47°F)
3.2
3.2
3.2
BTU/hr (17°F)
82,000
82,000
82,000
COP (17°F)
2.1
2.1
2.1
Evapoartor Motor / Coil
Motor Type (Belt Drive)
AX49
AX49
AX49
Indoor Nominal CFM
5,000
5,000
5,000
Indoor Motor FLA (Cooling)
9.4
4.7
4.2
Horsepower - RPM
3.0 - 1,725
3.0 - 1,725
3.0 - 1,725
Piston Size (Cooling)
0.096
0.096
0.096
Filter Size (Qty)
(4) 20" x 25" x 2"
(4) 20" x 25" x 2"
(4) 20" x 25" x 2"
Drain Size (NPT)
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1 & #2 (oz.)
290 / 290
290 / 290
290 / 290
Evaporator Coil Face Area (ft²)
14.7
14.7
14.7
Rows Deep / Fins per Inch
4 / 15
4 / 15
4 / 15
# of Wheels (D x W)
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
Motor Sheave / Blower Sheave
VL40 / AK66
VL40 / AK66
VL40 / AK66
Condenser Fan / Coil
Quantity of condenser Fan Motors
2
2
2
Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22/ 3
22/ 3
22/ 3
Outdoor Nominal CFM
7,200
7,200
7,200
Face Area (ft²)
35.3
35.3
35.3
Rows Deep / Fins per Inch
2/3 rows 15 fpi
2/3 rows 15 fpi
2/3 rows 15 fpi
Piston Size (Heating)
0.067
0.067
0.067
Compressor
Quantity / Stage
2 / Single
2 / Single
2 / Single
Type
Scroll
Scroll
Scroll
Compressor RLA / LRA ea.
22.4 / 149
10.6 / 75
7.7 / 54
Electrical Data / Static
Voltage / Phase / Frequency
208-230/ 3/ 60
460/ 3/ 60
575/ 3/ 60
Standard Max Static
1.4"
1.4"
1.4"
Outdoor Fan FLA ea.
2.4
1.2
0.9
Total Unit Amps
59
28
21.4
Min. Circuit Ampacity¹
65
31
23
Max. Overcurrent Protection (amps)²
80
40
30
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
1325
1325
1325
Ship Weight (lbs)
1350
1350
1350
¹  Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
²   May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.