Below is an overview for the connection of the  Indoor unit to the Outdoor unit. 
OVERVIEW
This appliance must be installed according to national power supply acquirement.
Drain
Hose
Ground Wire
(Not Supplied)
5/8" side piping
Oxygen tube
Connecting
cable
3/8" side piping
Drain Hose
Pipes
(Not Supplied)
Wall
Bracket
AC
Connection
(Not Supplied)
Wrap with
Tape
AC Outlet
and Plug
Copper
Tubing
10cm (3.95in) 
from ceiling
At least 30cm
(11.8in) from unit
30cm (11.8in) from
side wall
10cm (3.95in) from
side wall
Maximum Height
7M (21Ft)
Maximum Length
15M (49Ft)
Any tube length between 7 and 15 meters must
be precharged with freon using the following calulation:
(Length – 5) x 30 grams
Adding additonal tubing will decrease efficiency
10
cm
70
cm
60
cm
3.9 inches
23.6 
inches
60
cm
23.6 
inches
27.6
inches
Plug into 220V~240V
AC Outlet
5/8" side piping
Connecting
cable
3/8" side piping
Drain Hose
Cooling Only
* DSB-183AH model has oxygen tube, but DSB-F183L, 183LH, 183PH models do not.
Heating & Cooling
NOTES:
 After installation it must be
possible for the user to dis -
connect the power supply
plug.
 If the AC outlet is a 3-
pronged type or other, have
an electrician install a new
outlet.
 Contanct service man when
replace the power cord set.
 The specification of AC con -
nection is 2.0mm
2
x 3C x 6m.
INSTRUCTION OF INSTALLATION
Wall
Wall Cap
Oxygen tube
Drain
Hose
Oxygen tube
17