Emerson Figure i User Manual

Page of 36
Installation
22
2.7
Electrical Data
Table 16
Electrical data—Standard sound and ambient models (95°F/35°C) 60Hz
Model # 
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage- Phase
208/230-1
208/230-3
460-3
575-3
14
1
FLA
8.4
WSA
10.2
OPD
15
20
1.5
FLA
12.1
WSA
14.8
OPD
25
27
2
FLA
13.5
WSA
16.5
OPD
25
37
3
FLA
19.3
12.8
6.4
5.9
WSA
23.8
15.7
7.8
7.1
OPD
40
25
15
15
42
3.5
FLA
15.3
7.1
6.6
WSA
18.8
8.7
8.0
OPD
30
15
15
67
5
FLA
24.1
11.7
9.1
WSA
29.3
14.2
11.1
OPD
45
20
15
96
8
FLA
35.6
17.4
13.5
WSA
40.8
19.9
15.4
OPD
60
25
20
FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)
Table 17
Electrical data—High ambient models (105°F/41°C) 60Hz
Model # 
Nominal
Capacity,
Tons
* Electrical
Characteristic
Input Voltage-Phase
208/230-1
208/230-3
460-3
575-3
37
3
FLA
21.3
14.8
7.4
5.9
WSA
25.8
17.7
8.8
7.1
OPD
40
25
15
15
42
3.5
FLA
17.3
8.1
6.6
WSA
20.8
9.7
8.0
OPD
30
15
15
67
5
FLA
24.2
11.7
9.3
WSA
29.4
14.2
11.3
OPD
50
20
15
FLA = Full Load Amps
WSA = Wire Size Amps (minimum supply circuit current capacity)
OPD = Overcurrent Protection Device (fuse or circuit breaker)