Friedrich H)A09K25 User Manual

Page of 44
24
Emergency Heat Switch (Defrost Thermostat) Continuity Check
Electric Heat Switch Operation 
(Heat Pumps Only)
The electric heat switch is a dual function control and is 
shown on the wiring diagram as a defrost thermostat. 
It may be adjusted using a screwdriver.  As the control 
shaft is rotated counter clockwise a detent will be 
encountered. Turning the control past the detent will lock 
out the compressor and acts as an emergency heat switch. 
Turning the control shaft clockwise will lower the change 
over point for compressor operation. The control it self is 
a double throw, single pole switch operated by a bellows 
and a gas fi lled capillary tube. The capillary tube senses 
a combination of outdoor coil temperature and outdoor air 
temperature.  As the combined temperatures reach a point 
that the outdoor coil is iced, where heat pump operation 
is no longer effi cient, the control shuts off the compressor 
and turns on the electric heat.  At its lowest setting the cut 
off point is approximately 25 degrees, the highest setting 
is 52 degrees, with a 10 degree differential.  It is possible, 
under certain conditions, for the unit to cycle between 
compressor and electric heat operation.
Electric Heat Switch Check Out
The switch may be checked out with an ohmmeter.  
Remove and label the three wires from the switch. 
Terminal 2 is common and the contacts make to Terminal 
3 on temperature rise and to Terminal 1 on temperature 
fall.  With the control set in the emergency heat position 
continuity should be read between Terminal 2 and Terminal 
1 regardless of coil temperature.  As the control shaft is 
rotated clockwise, through the adjustment range, continuity 
will be read between Terminal 2 and Terminal 3, providing 
the temperature of the capillary tube is above 25º (± 5%).  If 
the temperature at the capillary tube is above approximately 
52 degrees it may be necessary to place the end of the 
capillary tube in ice water to determine if the control is 
sensing temperature changes.  Should the control lose the 
gas charge in the capillary tube it will fail to the electric heat 
position and the compressor will not operate.
SWITCH POSITION
TEMPERATURE AT CAPILLARY
CONTINUITY READ
EMERGENCY HEAT
N/A
1 and 2 = Electric Heat
ANYWHERE IN 
ADJUSTMENT RANGE
ABOVE SET POINT
2 and 3 = Compressor
ANYWHERE IN 
ADJUSTMENT RANGE
BELOW SET POINT
1 and 2 = Electric Heat