Perform the electric safe check after 
completing installation:
1. Insulated resistance
    The insulated resistance must be more than 
    2M .
2. Grounding work 
    After finishing grounding work, measure the 
    grounding resistance by visual detection and 
    grounding resistance tester. Make sure the 
    grounding resistance is less than 4 . 
3. Electrical leakage check (performing during 
    test running)
    During test operation after finishing installation, 
    the serviceman can use the electroprobe and 
    multimeter to perform the electrical leakage 
    check. Turn off the unit immediately if leakage 
    happens. Check and find out the solution 
    ways till the unit operate properly.
A: Lo packed valve  B: Hi packed valve 
C and D are ends of indoor unit connection.
CAUTION
    Electrical safety check
    Gas leak check
1. Soap water method:
     Apply a soap water or a liquid neutral 
    detergent on the indoor unit connection 
    or outdoor unit connections by a soft 
    brush to check for leakage of the 
    connecting points of th piping. If bubbles
    come out, the pipes have leakage.
2. Leak detector
Use the leak detector to check for leakage.
Safety and leakage check
15
Indoor unit 
check point
Outdoor unit 
check point 
n m k
j i h
A
B
C
a
c
b
d
e
f
               a,b,c,d,h,i,j , k are points for  one-two type.
a,b,c,d,e,f,,h,i,j,k,m,n are points for one-three type.
Indoor unit 
check point
Outdoor unit 
check point 
               One-four type
30
 AIR PURGING
Fig.63
Fig.64
NOTE: The illustration is for explanation 
purpose only. The actual order of  A, B, C
and D on the machine may be slightly 
different from the unit you purchased. The 
actual shape shall prevail.
Air Purging
NOTE: The illustration is for explanation
purposes only. The actual order of A, B, C
and D on the machine may be slightly
different from the unit you purchased. The
actual shape shall prevail.
Apply a soap water or a liquid neutral
detergent on the indoor unit connection
or outdoor unit connections with a soft
brush to check for leakage of the
connecting points of th piping. If bubbles
come out, the pipes have leakage.
test run).
Refrigerant Leak Check
Safety and Leak Check