10-9. USEFUL FUNCTIONS
  For this outdoor unit, by referring to the 5 LED (Red) indicator lights, self-diagnosis is possible.
  LEDS (Red, D09 to D13) are located on the sub-control board underneath the inverter.
  These LEDs do not normally light.
1.
If trouble occurs, LED (Red) goes on according to the contents of trouble 
as shown in the table above.
2.
When two or more troubles occur, LEDs go on cyclically (alternately).
3.
When the trouble is eliminated, LEDs (Red) go off.
Self-Diagnosis by LED Indication
Contents
Indoor alarm 
code
LED indication
D09
D10
D11
D12
D13
Normal running
None
IGBT short circuit, Compressor motor rear short
14
Trouble on position detecting circuit
16
Trouble on current detecting circuit
17
CONDENSOR PIPE TEMP. SENSOR(TE) fault
18
SUCTION PIPE TEMP. SENSOR(TS) fault
18
DISCHARGE PIPE TEMP. SENSOR(TD) fault
19
Trouble on outdoor fan
1A
OUTDOOR TEMP. SENSOR(TO) fault
1B
Trouble on compressor system
1C
GAS SIDE PIPE TEMP. SENSOR a (TGa) fault
1C
GAS SIDE PIPE TEMP. SENSOR b (TGb) fault
1C
TGa, TGb sensor out of place, PMV fault
1C
Communication trouble between MCU
1C
Compressor lock
1D
Trouble on discharge temp. Gas leakage
1E
Compressor break down
1F
 : LED ON, 
 : LED OFF
D09 D10 D11 D12 D13 
LED (Red) 