– 82 –
9.  SETUP AT LOCAL SITE AND OTHERS
1. Display range on remote controller
The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the
master unit is reflected on the remote controller.
2. Address setup
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic
address.  If power of the indoor unit is not turned on within 3 minutes (completion of automatic address
setting), the system is rebooted and the automatic address setting will be judged again.
1) Connect 3 In/Out cables surely.
2) Check line address/indoor address/group address of the unit one by one.
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the
unit No. is not duplicated with one of another unit.
OUT
IN
Remote controller
1-1
OUT
IN
2-1
Master
OUT
IN
3-1
OUT
IN
4-1
OUT
IN
7-1
Max. 8 units
1    2    3
<Operation procedure>
Returned to usual display
2
3 1
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT  LOUVER
T
9-1. Calling of Error History
<Contents>
The error contents in the past can be called.
<Procedure>
1
Push 
SET
 + 
TEST
 buttons simultaneously for
4 seconds or more to call the service check mode.
Service Check goes on, the CODE No. 01  is displayed, and then
the content of the latest alarm is displayed. The number and error
contents of the indoor unit in which an error occurred are dis-
played.
2
In order to monitor another error history, push the set
temperature 
 / 
 buttons to change the error
history No. (CODE No.).
CODE No. 
  (Latest) → CODE No. 
"
 (Old)
NOTE : 4 error histories are stored in memory.
3
Pushing 
TEST
 button returns the display to usual display.
REQUIREMENT
Do not push 
CL
 button, otherwise all the error histories of the indoor
unit are deleted.
9-2. Group Control Operation
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.
The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to
setting on the remote controller.
<System example>