Toshiba RAV-SM802UT-E User Manual

Page of 196
– 108 –
Item No. (DN) table (Selection of function)
DN
01
02
03
06
0F
10
11
12
13
14
19
1E
28
2A
2b
2E
30
31
32
33
40
5d
60
8b
Item
Filter sign lighting
time
Dirty state of filter
Central control
address
Heating suction temp
shift
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Temp difference of
automatic cooling/
heating mode
selection COOL 
HEAT, HEAT 
COOL
Automatic restart of
power failure
Option
Thermo output
selection (T10 
ƒ
)
Option
Option
Option
Sensor selection
Temperature
indication
Option
High ceiling selection
(Air volume selection)
Timer set
(Wired remote
controller)
Correction of high
heat feeling
Description
0000 : None
0002 : 2500H (4-Way/Duct/Ceiling Type)
0000 : Standard
0001 : High degree of dirt
(Half of standard time)
0001 : No.1 unit
to
0064 : No.64 unit
0099 : Unfixed
0000 : No shift
0001 : +1°C
0002 : +2°C
to
0010 : -10°C
(Up to recommendation + 6)
0000 : Heat pump
0001 : Cooling only
(No display of [AUTO] [HEAT])
0001 : SM562/802UT type
0004 : SM562/802/1102/1402BT type, SP1102UT-E
0007 : SM562/802/1102/1402CT type
0038 : SM1100/1400UT type
0000 : Unfixed
0009 : 562 type
0012 : 802 type
0015 : 1102 type
0017 : 1402 type
0001 : No.1 unit
to
0030 : No.30 unit
0001 : No.1 unit
to
0064 : No.64 unit
0000 : Individual
0001 : Master of group
0002 : Sub of group
0000 : 0 deg
to
0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0001 : Restart
0000 : Indoor thermo ON
0001 : Output of outdoor comp-ON receiving
0000 : Body TA sensor
0001 : Remote controller sensor
0000 : °C (celsius)
0001 : °F (Fahrenheit)
0000 : Standard filter
0001 : Oil guard, Super-long life, Optical regenerative deodorization
0003 : High performance (65%), High performance (90%),
High antibacterial performance (65%)
0000 : Available (Operable)
0001 : Unavailable (Operation prohibited)
0000 : None
0001 : Correction
At shipment
0002 for D.I. and S.D.I.
models
0000 : Standard
0099 : Unfixed
0002 : +2°C
(Floor type 0000: 0°C)
0000 : Shared for cooling/
heating
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : Default
0000: Thermo. ON
0000 : Default
0000 : Default
0000 : Default
0000 : Body sensor
0000 : °C
0003 : Default
0000 : Standard
0000 : Available
0000 :  None