4. Wiring Specifications
• Use 2-core with no polar wire.
• Match the length of wire to wire length of the central
control system.
If mixed in the system, the wire length is
lengthened with all indoor/outdoor inter-unit wire length at side.
• To prevent noise trouble, use 2-core shield wire.
• Connect the shield wire by closed-end connection and apply open process (insulating process) to the last terminal.
Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter unit setup)
No. of wires
2
Size
Up to 1000m: twisted wire 1.25mm
2
Up to 2000m: twisted wire 2.0mm
2
5. P.C. Board Switch  (SW01) Setup
When performing collective control by customized setup only, the setup of terminator is necessary.
• Using SW01, set up the terminator.
• Set up the terminator to only the adapter connected to the indoor unit of least line address No.
Central control device
U1
U3
U2
U4
Central control device
U1
U3
1 2 3
U2
U4
Central control devices: Max. 10 units
Refrigerant line 1
Outdoor unit
Indoor unit
1 2 3
Refrigerant line 2
1 2 3
Refrigerant line 3
1 2 3
Refrigerant line 4
1 2 3
A B
U3 U4
1 2 3
A B
U3 U4
1 2 3
A B
1 2 3
A B
1 2 3
A B
1 2 3
A B
U3 U4
TCC-LINK adapter
This product
sold separately
(                    )
Remote controller
Indoor/outdoor inter-unit wire (AC230V serial)
Central control system wiring
Master unit
Master 
unit
Sub unit
Sub unit
Sub 
unit
* Wiring for No.1 and 2 only
Remote controller
Remote controller
Remote controller
Remote controller
Remote controller wiring
Group operation (Max. 8 units)
Twin/Triple operation (Example of triple)
(OFF at shipment from factory)
(OFF at shipment from factory)
Line address
SW01 Bit 1
SW01 Bit 2
Remarks
1
ON
OFF
Turn SW01 Bit 1 to ON.
2
OF
OFF
As status shipped from factory
4
OF
OFF
As status shipped from factory
(Reference) Setup contents of switch
SW01
Bit 1
OFF
ON
OFF
ON
Bit 1
OFF
OFF
ON
ON
Terminator
None
100
Ω
75
Ω
43
Ω
Remarks
Mixed with multi (Link wiring) at shipment from factory 
Central control by digital inverter only 
Spare 
Spare
Central control device
U1 U2
1 2 3
Outdoor unit
Indoor unit
1 2 3
1 2 3
1 2 3
1 2 3
A B
U3 U4
1 2 3
A B
U3 U4
1 2 3
A B
1 2 3
A B
1 2 3
A B
1 2 3
A B
U3 U4
Caution 1
Remote controller
Central control system wiring
Master unit
Master
unit
Sub unit
Sub unit
Sub unit
Caution 2
Remote controller
Remote controller
Remote controller
(Group operation)
(Triple operation)
Caution 3
: TCC-LINK adapter 
 (This option)
Earth terminal
CAUTION
1) Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)
2) Apply open process to the last terminal (insulating process).
3) Ground earth wire to 1 point at indoor unit side.