9-2. Outdoor Controls
9-2-1. Print Circuit Board
P.C. Board Comparison Table for Digital Inverter
1: Applied
Regarding diagram for MCC-1359 / MCC-1438, refer to Appendix-2.
9-1-2. Indoor P.C. Board Optional Connector Specifications
Function
Option output
Outside error
input
Filter option
error
CHK
Operation check
DISP display
mode
EXCT demand
Connector
No.
CN60
CN80
CN70
CN71
CN72
CN73
Pin
No.
1
2
3
4
5
6
1
2
3
1
2
1
2
1
2
1
2
Specifications
DC12V (COM)
Defrost output
Thermo. ON output
Cooling output
Heating output
Fan output
DC12V (COM)
DC12V (COM)
Outside error input
Filter/Option/Humidifier
setup input
0V
Check mode input
0V
Display mode input
0V
Demand input
0V
Remarks
ON during defrost operation of outdoor unit
ON during Real thermo-ON (Comp ON)
ON when operation mode is in cooling system
(COOL, DRY, COOL in AUTO cooling/heating)
ON when operation mode is in heating system
(HEAT, HEAT in AUTO cooling/heating)
ON during indoor fan ON
(Air purifier is used/Interlock cable)
(When continued for 1 minute)
Check code “L30” is output and forced operation stops.
Option error input is controlled. (Protective operation
for device attached to outside is displayed.)
* Setting of option error input is performed from remote
controller. (DN=2A)
Used for operation check of indoor unit.
(Communication with outdoor unit or remote controller
is not performed, but the specified operation such as
indoor fan “H” or drain pump ON is output.)
Display mode enables indoor unit and remote controller
to communicate. (When power is turned on)
Forced thermo-OFF operation in indoor unit
P.C. board
Main
MCC-5009
Sub
MCC-1530
CDB
MCC-1531
IPDU MCC-1438
Part No.
4316V284
4316V293
4316V283
4316V282
4316V291
4316V278
Model name   RAV -SM
562AT-E/802AT-E
1102AT-E/1402AT-E
1
1
1
1
Model name   RAV -SP
562AT-E/802AT-E
1102AT-E/1402AT-E
1
1
1
1