Toshiba RAV-SM802UT-E User Manual

Page of 196
– 86 –
Check item code [14].
Correct inter-unit cable.
Correct connection of connector.
Check/Correct charged 
refrigerant amount.
Check indoor P.C. board (MCC-1402).
Defect 
®
 Replace
Check outdoor P.C. board
Defect 
®
 Replace
MCC-5009
MCC-1531 and MCC-1438
RAV-SM562AT-E
RAV-SM802AT-E
RAV-SM1102AT-E
RAV-SM1402AT-E
RAV-SP562AT-E
RAV-SP802AT-E
RAV-SP1102AT-E
RAV-SP1402AT-E
Does outdoor unit operate?
Is setup of group address correct?
Does case thermo. operate?
Are 1, 2, 3 inter-unit cables normal?
Are connections from connectors
of inter-terminal blocks (1, 2, 3)
of indoor/outdoor units normal?
Does voltage between
2 and 3 of inter-terminal blocks (1, 2, 3)
of indoor unit vary?*
Check indoor P.C. board 
(MCC-1402).
Defect 
®
 Replace
*
As shown in the following figure, perform measurement 
within 20 seconds after power ON.
Black
White
3
2
1
Inter-terminal block
S5277G
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
NO
YES
[E04 error]