York YPAL 050 User Manual

Page of 168
103
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
6
ADDRESS
NUMBER
DESCRIPTION
UNITS OF ADJUSTMENT
RANGE OF 
ADJUSTMENT
CURRENT 
SETTING
72/73/74/
75/76
ALARM ARRAY
DATA - 5 CHARACTERS
0 - 255
0
77
VAV / CV SELECTION
READ ONLY FLAG
CV = 0
VAV = 1
0
78
HOT GAS REHEAT
PARAMETER BIT
0 = OFF, 1 = ON
OFF
79
HOT GAS PRESENT ON COMPRESSOR # 1
PARAMETER BIT
0 = OFF, 1 = ON
OFF
80
COMPRESSORS AVAILABLE FOR COOLING
PARAMETER BIT
2 - 4
2
81
STAGES OF HEAT AVAILABLE
PARAMETER BIT
0 - 3
0 = DISABLED
2
82
DUCT STATIC READING
PRESSURE - INCHES OF 
H2O
0.000 - 5.000
0000
83
BUILDING STATIC PRESSURE
PRESSURE - INCHES OF 
H2O
0.000 - 5.000
0000
84
LOW AMBIENT KIT INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
85
BUILDING STATIC PRESSURE SENSOR INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
86
ERV INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
87
ERV UNOCCUPIED FAN ENABLE
PARAMETER BIT
0 = OFF, 1 = ON
OFF
88
DUCT STATIC SHUTDOWN SETPOINT
PRESSURE - INCHES OF 
H2O
0.000 - 5.000
4.500
TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)