Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
YCJD42S41S1(H)
INDOOR COIL MODEL NO.
FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1200
1400
1600
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
44.4 45.5 43.6 47.0 48.5 45.9 46.5 45.0 48.5 49.8 47.5 47.5 46.5 50.1 51.1 
S.C.
41.5 35.6 29.7 28.7 21.5 42.9 37.5 31.4 30.2 22.9 44.4 39.4 33.2 31.7 24.3 
KW
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6 
75
T.C.
42.3 42.9 41.2 45.1 46.6 44.2 44.3 42.7 46.6 47.9 46.0 45.7 44.2 48.1 49.1 
S.C.
39.4 35.2 29.2 28.5 21.3 41.1 37.4 31.1 30.1 22.4 42.9 39.7 33.0 31.8 23.6 
KW
2.7 2.7 2.7 2.8 2.8 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.9 
85
T.C.
40.2 40.3 38.9 43.3 44.6 42.4 42.1 40.4 44.7 45.9 44.6 43.9 41.9 46.0 47.2 
S.C.
37.2 34.7 28.7 28.2 21.2 39.3 37.3 30.8 30.0 22.0 41.5 40.0 32.9 31.8 22.9 
KW
3.0 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1 
95
T.C.
38.2 37.7 36.5 41.5 42.7 40.7 39.9 38.0 42.0 44.0 43.2 42.1 39.6 43.9 45.3 
S.C.
35.0 34.3 28.1 28.0 21.0 37.5 37.3 30.5 29.4 21.6 40.0 40.3 32.8 31.9 22.2 
KW
3.2 3.2 3.2 3.3 3.4 3.3 3.3 3.3 3.3 3.4 3.3 3.3 3.3 3.4 3.4 
105
T.C.
35.3 34.7 32.8 37.4 38.7 37.5 36.7 34.2 38.6 39.8 39.8 38.8 35.6 39.8 40.9 
S.C.
32.3 32.1 26.5 26.4 19.6 34.5 34.5 28.8 28.4 20.4 36.7 37.0 31.1 30.5 21.2 
KW
3.5 3.5 3.5 3.6 3.7 3.5 3.5 3.5 3.6 3.7 3.6 3.6 3.5 3.6 3.7 
115
T.C.
32.4 31.7 29.2 33.4 34.8 34.5 33.6 30.5 34.6 35.7 36.5 35.5 31.8 35.7 36.7 
S.C.
29.7 30.0 25.0 24.9 18.2 31.6 31.9 27.2 27.0 19.3 33.5 33.8 29.4 29.1 20.3 
KW
3.7 3.7 3.7 3.8 4.0 3.8 3.8 3.7 3.8 4.0 3.8 3.8 3.7 3.9 4.0 
125
T.C.
29.6 28.8 25.6 29.4 30.9 31.4 30.5 26.8 30.5 31.7 33.2 32.2 28.0 31.7 32.5 
S.C.
27.1 27.9 23.5 23.4 16.8 28.7 29.3 25.6 25.6 18.1 30.2 30.6 27.6 27.8 19.4 
KW
4.0 4.0 3.9 4.0 4.2 4.0 4.0 4.0 4.1 4.3 4.1 4.1 4.0 4.1 4.3 
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
FC/MC/PC48 
1.00 1.00 1.00 
HC42 
1.00 1.00 1.00 
UC48 
1.00 1.00 1.00 
AHP42 
0.97 1.00 0.97 
MV16C 
FC/MC43C 
1.00 1.02 0.91 
MA16C 
FC/MC43C 
1.00 1.00 1.00 
MV16C 
FC/MC48C 
1.00 1.02 0.91 
MV20D 
FC/MC48D 
1.00 1.02 0.91 
MA14D 
FC/MC48D 
1.00 1.00 1.00 
MA16C 
FC/MC48C 
1.00 1.00 1.00 
F5FP048 
1.00 1.00 1.00 
Variable Speed 
Furnace
Coil
T.C.
S.C.
KW
PV8*B16
FC/MC/PC43B 1.00 
1.01 
0.91 
PV8*C20
FC/MC/PC43C 1.00 
1.02 
0.91 
P(C,V)9*C16
FC/MC/PC43C 1.00 
1.01 
1.00 
P(C,V)9*C20
FC/MC/PC43C 1.00 
1.02 
0.91 
PV8*C16
FC/MC/PC48C 1.00 
1.01 
0.91 
PV8*C20
FC/MC/PC48C 1.00 
1.02 
0.91 
P(C,V)9*C16
FC/MC/PC48C 1.00 
1.01 
1.00 
P(C,V)9*C20
FC/MC/PC48C 1.00 
1.02 
0.91 
P(C,V)9*D20
FC/MC/PC48D 1.00 
1.02 
0.91 
PV8*C16
HC42 1.00 
1.01 
0.91 
PV8*C20
HC42 1.00 
1.02 
0.91 
P(C,V)9*C16
HC42 1.00 
1.01 
1.00 
P(C,V)9*C20
HC42 1.00 
1.02 
0.91