• FILTER OPTIONS - Standard units are shipped with 2” 
throw-away filters installed. 2” pleated and 4” pleated 
filters are offered as a factory installed option.
• CONVENIENCE OUTLET - This 110 volt outlet can be 
“powered” by the unit with a stepdown transformer or you 
may order the unit with a “non-powered” convenience 
outlet that can be wired in the field.
• DISCONNECT SWITCH - For gas heat units and cooling 
units with electric heat, a HACR breaker sized to the unit 
is provided. For cooling only units, a switch sized to the 
largest electric heat available for the particular unit is 
provided. Factory installed option only.
• DOUBLE WALL CONSTRUCTION - Optional double wall 
construction is available to provide smooth inner surfaces 
for easy and effective cleaning to reduce risk of dirt and 
bacterial accumulation. Fiberglass insulation is 
sandwiched between heavy gauge steel sheets to form a 
durable, rigid casing to withstand higher working 
pressures and impact forces. The heavy-duty construction 
provides excellent acoustic and thermal insulation and 
eliminates erosion of insulation material and 
contamination of the air stream.
• BAS - Building Automation System Controls 
(available on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York® 
Simplicity® INTELLI-Comfort™ control is factory installed. It 
includes a supply air sensor, a return air sensor, and an out-
side air sensor. There are provisions for a field installed dirty 
filter indicator switch, an air-proving switch, an Outside Air 
Humidity sensor, a Return Air Humidity sensor, an Inside IAQ 
sensor, and an Outside Air IAQ sensor. Construction mode 
operation, 365-day real time clock with 7 day programming 
plus holiday scheduling is built-in. Two different modes of 
demand ventilation are achieved through the INTELLI-Com-
fort™ using CO
2
 sensors. It uses an inside CO
2
 sensor to 
perform Demand Ventilation. It can also use an Outside CO
2
 
sensor to perform Differential Demand Ventilation. It uses a 
Patented Comfort Ventilation algorithm to provide comfort-
able ventilation air temperature. The patented economizer-
loading algorithm will protect the equipment when harsh 
operating conditions exist. Humidity in the occupied space or 
return duct can be monitored and controlled via humidity 
sensors and the on-board connection for hot gas re-heat 
system. It uses the INTELLI-Start™ algorithm to maximize 
energy savings by recovering the building from the Unoccu-
pied Setpoints to the Occupied Setpoints just in time for the 
Occupied Time Period to begin. The Simplicity® INTELLI-
Comfort™ balances space temperature, ventilation air tem-
perature, CO
2
 and humidity for ultimate comfort.
Simplicity® INTELLI-Comfort™ with ModLINC CON-
TROL - 
The York® Simplicity® INTELLI-Comfort™ with 
ModLINC control is factory installed. It includes all the fea-
tures of the INTELLI-Comfort™ control with an additional 
control to translate communications from MODBUS to the 
BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building 
automation system controller is factory installed. Includes 
supply air sensor, return air sensor, dirty filter indicator 
switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson 
Control YK-UNT-1126 building automation system control-
ler is factory installed. Includes supply air sensor, return air 
sensor, dirty filter indicator switch, and air proving switch.
CPC BAS CONTROL - The Computer Process Controls 
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes sup-
ply air sensor, return air sensor, dirty filter indicator switch 
and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell W7750C 
building automation system controller is factory installed. 
Includes air supply sensor, return air sensor, dirty filter 
indicator switch, and air proving switch.
• COIL GUARD - Customers can purchase a coil guard kit 
to protect the condenser coil from damage. This is not a 
hail guard kit.
• SMOKE DETECTORS - (supply air & return air) The 
smoke detectors stop operation of the unit by interrupting 
power to the control board if smoke is detected within the 
air compartment.
• STAINLESS STEEL HEAT EXCHANGER - For 
applications in corrosive environments, this option 
provides a full stainless steel heat exchanger assembly.
• STAINLESS STEEL DRAIN PAN - An optional rust-proof 
stainless steel drain pan is available to provide years of 
trouble-free operation in corrosive environments.
• PHASE MONITORS - Designed to prevent unit damage. 
The phase monitor will shut the unit down in an out-of-
phase condition.
• HIGH STATIC DRIVE - May include a belt, blower pulley, 
motor pulley or a motor change to enhance blower 
performance.
• LOW STATIC DRIVE - May include a belt, blower pulley, 
motor pulley or a motor change when standard airflow is 
not required. (WR300 & WR240 only)
• DIRTY FILTER SWITCH - This kit includes a differential 
pressure switch that energizes the fault light on the unit 
thermostat, indicating that there is an abnormally high 
pressure drop across the filters. Factory installed option or 
field installed accessory.
• HINGED FILTER DOOR/”TOOL FREE” BLOWER AND 
ACCESS PANELS (not hinged) - This option allows for 
easy access and maintenance.
Factory installed smoke detectors in the return air, 
may be subjected to freezing temperatures during 
“off” times due to out side air infiltration. these smoke 
detectors have an operational limit of 32°F to 131°F. 
smoke detectors installed in areas that could be out 
side those limitations will have to be moved to 
prevent having false alarms.