PHYSICAL AND ELECTRICAL DATA - 1 PHASE
MODEL
H2RD018S06 H2RD024S06 H2RD030S06 H2RD036S06 H2RD042S06 H2RD048S06 H2RD060S06
Unit Supply Voltage
208-230V, 1
φ, 60Hz
Normal Voltage Range 
1
187  to 252
Minimum Circuit Ampacity
9.4
11.8
15.1
18.3
18.3
30.3
32.7
Max. Overcurrent Device Amps 
2
15
20
25
30
30
50
50
Min. Overcurrent Device Amps 
3
15
15
20
20
20
35
35
Compressor Type 
4
Recip
Recip
Recip
Recip
Recip
Scroll 
B
Scroll 
B
Compressor 
Amps
Rated Load
6.4
9.0
10.7
13.4
13.5
23.0
25.0
Locked Rotor
36
48
61
78
78
115
150
Crankcase Heater
No
No
No
No
No
No
No
Fan Motor Amps Rated Load
0.8
0.5
1.5
1.5
1.5
1.5
1.5
Fan Diameter Inches
18
22
22
22
22
24
24
Fan Motor
Rated HP
1/8
1/15
1/4
1/4
1/4
1/4
1/4
Nominal RPM
1075
850
850
850
850
850
850
Nominal CFM
2150
2,200
3100
3150
3550
3550
3600
Coil
Face Area Sq. Ft.
11.43
15.72
15.72
15.72
23.60
24.00
27.00
Rows  Deep
1
1
1
1
1
1
1
Fin / Inches
22
18
22
22
22
22
22
Liquid Line OD (Field Installed)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line OD (Field Installed)
3/4
3/4
3/4
7/8
7/8
7/8
1-1/8
Unit Charge (Lbs. - Oz.) 
5
4 - 9
5 - 8
5 - 13
6 - 0
8 - 13
8 - 6
10 - 2
Charge Per Foot, Oz.
0.68
0.68
0.70
0.70
0.70
0.70
0.76
Operating Weight Lbs.
151
151
183
183
193
215
220
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
C
A
B
DIMENSIONS
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
* Adapter fitting required for 1-1/8” line set.
B
C
Liquid
Vapor
018
23
35
23
3/8”
3/4”
024
27
37
27
030
27
37
27
036
27
37
27
7/8”
042
39
37
27
048
34
43
32
060
38
43
32
7/8”*