York H*RD018 THRU 060 User Manual

Page of 24
254892-YTG-C-0606
                            
22
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
*
= Single-phase outdoor units only.
*
= Single-phase outdoor units only.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H2RD048S06, H1RD048S(25,46) **
INDOOR COIL MODEL NO.
FC/MC/PC/UC48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1400
1600
1800
ID 
DB 
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID 
WB 
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 
65
T.C.
45.9 49.0 47.2 51.9 54.5 48.7 50.8 48.2 52.9 54.7 51.5 52.5 49.2 53.9 54.9 
S.C.
44.2 41.8 34.6 34.7 27.5 45.8 44.4 36.9 36.9 28.2 47.5 47.0 39.2 39.0 29.0 
KW
2.6 2.6 2.6 2.7 2.7 2.6 2.6 2.6 2.7 2.7 2.6 2.6 2.6 2.7 2.7 
75
T.C.
44.6 47.5 45.7 50.3 52.8 47.4 48.9 46.5 51.0 53.0 50.1 50.4 47.4 51.7 53.2 
S.C.
42.9 41.2 34.0 34.2 26.9 44.5 43.7 36.2 36.3 28.0 46.1 46.1 38.5 38.4 29.0 
KW
3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 
85
T.C.
43.3 45.9 44.1 48.7 51.1 46.0 47.1 44.9 49.1 51.3 48.8 48.2 45.6 49.6 51.6 
S.C.
41.6 40.6 33.4 33.7 26.4 43.1 42.9 35.6 35.7 27.7 44.6 45.2 37.7 37.8 28.9 
KW
3.3 3.3 3.3 3.4 3.4 3.3 3.3 3.3 3.4 3.4 3.3 3.3 3.3 3.4 3.4 
95
T.C.
42.0 44.4 42.6 47.1 49.3 44.7 45.2 43.2 47.0 49.7 47.4 46.1 43.8 47.5 50.0 
S.C.
40.4 39.9 32.8 33.1 25.9 41.8 42.1 34.9 35.1 27.4 43.1 44.3 37.0 37.2 28.9 
KW
3.7 3.7 3.6 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 
105
T.C.
40.5 42.5 40.5 44.7 46.4 43.1 43.5 41.1 44.8 46.7 45.6 44.4 41.7 45.0 47.0 
S.C.
38.7 38.5 31.8 32.2 24.9 40.0 40.4 33.9 34.2 26.4 41.4 42.3 36.0 36.3 27.8 
KW
4.2 4.2 4.1 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 
115
T.C.
39.1 40.7 38.4 42.3 43.5 41.5 41.7 39.0 42.5 43.8 43.9 42.8 39.7 42.6 44.1 
S.C.
37.2 37.2 30.8 31.2 24.0 38.4 38.7 32.9 33.3 25.4 39.6 40.3 35.0 35.4 26.8 
KW
4.7 4.6 4.6 4.7 4.7 4.7 4.7 4.6 4.7 4.7 4.7 4.7 4.6 4.7 4.7 
125
T.C.
37.7 38.8 36.3 40.0 40.7 39.9 40.0 37.0 40.1 40.9 42.1 41.2 37.6 40.3 41.2 
S.C.
35.6 35.8 29.9 30.3 23.1 36.7 37.0 32.0 32.4 24.4 37.9 38.3 34.0 34.5 25.8 
KW
5.2 5.1 5.1 5.2 5.2 5.2 5.1 5.1 5.2 5.2 5.2 5.2 5.1 5.2 5.2 
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
**
For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.
Air Handler
Coil
T.C.
S.C.
KW
MA12C 
MC48C 
1.01 1.02 1.01 
MA20D 
MC48D 
1.00 1.00 1.00 
MA12C 
G*FD048H21 
1.01 1.02 1.01 
MA20D 
G*FD048H24 
1.00 1.00 1.00 
AHP/SHP48 
1.00 1.05 1.00 
F*FV060* 
1.01 1.05 1.01 
AHP/SHP60 
1.01 1.03 1.01 
MV16C* 
FC/MC48C 
1.00 0.99 1.00 
MV20D* 
FC/MC48D 
1.00 0.99 1.00 
AV/SV48* 
1.00 0.99 1.00 
HC48 
0.99 1.00 0.99 
HD48 
1.00 0.99 1.00 
G*FD048H21,24 
1.00 1.00 1.00 
Variable Speed 
Furnace *
Coil
T.C.
S.C.
KW
PV8*C16
FC/MC/PC48C 
0.99 0.97 0.99 
PV8*C20
FC/MC/PC48C 
1.00 1.00 1.00 
P(C,V)9*C16
FC/MC/PC48C 
1.00 1.00 1.00 
P(C,V)9*C20
FC/MC/PC48C 
1.00 1.00 1.00 
P(C,V)9*D20
FC/MC/PC48D 
1.00 1.00 1.00 
PV8*C16
HC48 
0.99 0.97 0.99 
PV8*C20
HC48 
1.00 1.00 1.00 
P(C,V)9*C16
HC48 
0.99 1.00 0.99 
P(C,V)9*C20
HC48 
0.99 1.00 0.99 
PV8*C16
HD48 
1.01 0.99 1.01 
PV8*C20
HD48 
1.01 1.02 1.01 
P(C,V)9*C16
HD48 
1.01 1.02 1.01 
P(C,V)9*C20
HD48 
1.01 1.02 1.01 
P(C,V)9*D20
HD48 
1.01 1.02 1.01