York H*RD018 THRU 060 User Manual

Page of 24
254892-YTG-C-0606
                            
6
Unitary Products Group
All dimensions are in inches. They are subject to change 
without notice. Certified dimensions will be provided upon 
request.
PHYSICAL AND ELECTRICAL DATA - 3 PHASE
MODEL
H1RD
030S25
H1RD
036S25
H1RD
042S25
H1RD
048S25
H1RD
060S25
H1RD
030S46
H1RD
036S46
H1RD
042S46
H1RD
048S46
H1RD
060S46
Unit Supply Voltage
208-230V, 3
φ, 60Hz
460V, 3
φ, 60Hz
Normal Voltage Range 
1
187 to 252
432 to 504
Minimum 
Circuit 
Ampacity
14.3 14.3 12.4 21.5 23.1  6.9  9.6  6.9  10.3 11.3 
Max. Overcurrent Device Amps 
2
20 20 20 35 40 15 15 15 15 15 
Min. Overcurrent Device Amps 
3
15
15
15
25
25
15
15
15
15
15
Compressor Type 
4
Recip Recip Recip ScrollB 
ScrollB Recip Recip Recip ScrollB 
ScrollB 
Compressor Amps
Rated 
Load
10.2 10.2 8.8 16.0 17.3 4.9 13.5 11.8 7.7  8.4 
Locked 
Rotor
72 72 72 115 
123 45 45 45 50 70 
Crankcase 
Heater
No No No No No No No No No No 
Fan 
Motor 
Amps
Rated 
Load
1.5 1.5 1.5 1.5 1.5 0.7 0.7 0.7 0.7 0.7 
Fan 
Diameter 
Inches
22 22 22 22 24 22 22 22 24 24 
Fan Motor
Rated 
HP
1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 
Nominal 
RPM
850 850 850 850 850 850 850 850 850 850 
Nominal 
CFM
3100 3150 3550 3550 3600 3100 3150 3550 3550 3600 
Coil
Face 
Area 
Sq. 
Ft.
15.72 15.72 23.60 24.00 27.00 15.72 15.72 23.60 24.00 27.00 
Rows 
Deep
1 1 1 1 1 1 1 1 2 2 
Fin 
Inches
22 22 22 22 22 22 22 22 18 18 
Liquid Line Set OD (Field Installed)
3/8 
3/8 
3/8 
3/8 
3/8 
3/8 
3/8 
3/8 
3/8 
3/8 
Vapor Line Set OD (Field Installed)
3/4 
7/8 
7/8 
7/8 
1-1/8 
3/4 
7/8 
7/8 
7/8 
1-1/8 
Unit Charge (Lbs. - Oz.) 
5
5 - 13 
6 - 0 
8 - 13 
8 - 6 
10 - 2 
5 - 13 
6 - 0 
8 - 13 
8 - 6 
10 - 2 
Charge 
Per 
Foot, 
Oz.
0.68 0.70 0.70 0.70 0.76 0.68 0.70 0.70 0.70 0.76 
Operating 
Weight 
Lbs.
208 208 208 215 294 208 208 215 250 294 
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
C
A
B
DIMENSIONS
Unit
Model
Dimensions
(Inches)
Refrigerant  Connection
Service Valve Size
A
1
1. Including Fan Guard.
* Adapter fitting required for 1-1/8” line set.
B
C
Liquid
Vapor
030
27
37
27
3/8”
3/4”
036
27
37
27
7/8”
042
39
37
27
048
34
43
32
060
38
43
32
7/8”*