York D2CE User Manual

Page of 24
036-21359-001-B-0302
6
Unitary Products Group
BLOWER PER FORM ANCE
 - 25 TON (DCE/DCG300)
BLOWER
PULLEY
SPEED 
TURNS
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
(rpm)
OPEN:
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
975
6.0*
1.4
5.9
4.9
1.0
7.3
6.0
0.5
8.8
7.2
-
-
-
-
-
-
1005
5.0
1.6
6.2
5.1
1.2
7.7
6.3
0.7
9.2
7.6
0.1
10.9
8.9
-
-
-
1040
4.0
1.8
6.6
5.4
1.4
8.1
6.7
0.9
9.7
8.0
0.3
11.4
9.4
-
-
-
1070
3.0
2.0
6.9
5.7
1.6
8.5
7.0
1.1
10.2
8.3
0.6
11.9
9.8
-
-
-
1100
2.0
2.1
7.3
6.0
1.8
8.9
7.3
1.3
10.6
8.7
0.8
12.4
10.2
0.2
14.3
11.7
1135
1.0
2.4
7.7
6.3
2.0
9.3
7.6
1.6
11.1
9.1
1.0
13.0
10.6
0.4
14.9
12.2
1165
0.0
2.6
8.0
6.6
2.2
9.7
8.0
1.8
11.6
9.5
1.3
13.5
11.0
0.7
15.5
12.7
1140
6.0
2.4
7.7
6.3
2.1
9.4
7.7
1.6
11.2
9.2
1.1
13.1
10.7
0.5
15.0
12.3
1180
5.0
2.7
8.2
6.7
2.3
9.9
8.1
1.9
11.8
9.7
1.4
13.7
11.2
0.8
15.8
12.9
1215
4.0
2.9
8.6
7.0
2.6
10.4
8.5
2.2
12.3
10.1
1.7
14.3
11.7
1.1
16.4
13.5
1255
3.0
3.2
9.1
7.4
2.9
11.0
9.0
2.5
12.9
10.6
2.0
15.0
12.3
1.4
17.2
14.1
1290
2.0
3.4
9.5
7.8
3.1
11.5
9.4
2.7
13.5
11.1
2.2
15.6
12.8
-
-
-
1330
1.0
3.7
10.0
8.2
3.4
12.0
9.9
3.0
14.1
11.6
2.6
16.4
13.4
-
-
-
1365
0.0
3.9
10.5
8.6
3.7
12.6
10.3
3.3
14.7
12.1
2.9
17.0
13.9
-
-
-
NOTES:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry  evaporator coil. 
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system.  All internal unit resistances have been deducted from the total static pressure of the 
blower.
* FACTORY SETTING
7500 CFM
8750 CFM
10000 CFM
11250 CFM
12500 CFM
STANDARD DRIVE:
ACCESSORY DRIVE:
DCE300 
- BOT TOM DUCT CON NEC TIONS
 (
COOL ING AP PLI CA TIONS)
BLOWER
PULLEY
SPEED 
TURNS
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
ESP 
OUTPUT
INPUT
(rpm)
OPEN:
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
(iwg)
(bhp)
(kW)
975
6.0*
1.2
5.9
4.9
0.5
7.3
6.0
-
-
-
-
-
-
-
-
-
1005
5.0
1.4
6.2
5.1
0.7
7.7
6.3
-
-
-
-
-
-
-
-
-
1040
4.0
1.6
6.6
5.4
0.9
8.1
6.7
0.2
9.7
8.0
-
-
-
-
-
-
1070
3.0
1.8
6.9
5.7
1.1
8.5
7.0
0.4
10.2
8.3
-
-
-
-
-
-
1100
2.0
2.0
7.3
6.0
1.3
8.9
7.3
0.6
10.6
8.7
-
-
-
-
-
-
1135
1.0
2.2
7.7
6.3
1.6
9.3
7.6
0.8
11.1
9.1
-
-
-
-
-
-
1165
0.0
2.4
8.0
6.6
1.8
9.7
8.0
1.0
11.6
9.5
0.2
13.5
11.0
-
-
-
1140
6.0
2.2
7.7
6.3
1.6
9.4
7.7
0.9
11.2
9.2
-
-
-
-
-
-
1180
5.0
2.5
8.2
6.7
1.9
9.9
8.1
1.2
11.8
9.7
0.3
13.7
11.2
-
-
-
1215
4.0
2.7
8.6
7.0
2.1
10.4
8.5
1.4
12.3
10.1
0.6
14.3
11.7
-
-
-
1255
3.0
3.0
9.1
7.4
2.4
11.0
9.0
1.7
12.9
10.6
0.9
15.0
12.3
-
-
-
1290
2.0
3.2
9.5
7.8
2.7
11.5
9.4
2.0
13.5
11.1
1.2
15.6
12.8
-
-
-
1330
1.0
3.5
10.0
8.2
3.0
12.0
9.9
2.3
14.1
11.6
1.5
16.4
13.4
-
-
-
1365
0.0
3.7
10.5
8.6
3.2
12.6
10.3
2.6
14.7
12.1
1.8
17.0
13.9
-
-
-
NOTES:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry  evaporator coil. 
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system.  All internal unit resistances have been deducted from the total static pressure of the 
blower.
* FACTORY SETTING
STANDARD DRIVE:
ACCESSORY DRIVE:
7500 CFM
8750 CFM
10000 CFM
11250 CFM
12500 CFM
BLOWER PERFORMANCE
 - 25 TON (DCE/DCG300)
DCG300 
- BOT TOM DUCT CON NEC TIONS
  (
COOL ING AP PLI CA TIONS)