Carrier 40RMS008-034 User Manual

Page of 48
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 534-00003
Printed in U.S.A.
Form 40RM-23SI
Pg CL-2
12-04
Replaces: 40RM-22SI
Book
1
4
Tab
3c 2e
Copyright 2004 Carrier Corporation
 -
 -
 - - - -
 -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 -
 - - - -
 -
 - - - -
 -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 -
 - - - -
 -
 - - - -
 -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 - - -
 - -
 -
 - - - -
 -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
 -
 - - - - -
 -
 - - - -
- - - - -
 -
 - - - -
 -
 -
 - - - -
 -
 -
 - - 
CUT
 AL
O
N
G DO
T
T
ED L
INE
CUT
 AL
O
N
G DO
T
T
ED L
INE
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:
AB ________ V 
AC ______ V 
BC ______ V
(AB + AC + BC)/3 = AVERAGE VOLTAGE = ________ V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = ________ V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = ___________ %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. START-UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST  10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT 
1
/
8
 to 
1
/
3
 FULL?
(Y/N) ______
NOTES:
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
______________________________________________________________________________________________________
COMP A1
COMP B1
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
INDOOR UNIT ENTERING WATER TEMP
(40RMS ONLY)
INDOOR UNIT LEAVING WATER TEMP
(40RMS ONLY)
COMPRESSOR AMPS (L1/L2/L3)
____/____/____
____/____/____