Carrier 50GL 024-060 User Manual

Page of 30
Table 4—ICM FIOP Physical Data—Unit 48JZ
THIS DATA APPLIES TO 48JZ UNITS WITH THE ICM INDOOR MOTOR FIOP
UNIT SIZE 48JZ
024040
030040
030060
036060
036090
042060
042090
NOMINAL CAPACITY (ton)
2
2-1/2
2-1/2
3
3
3-1/2
3-1/2
OPERATING WEIGHT (lb.)
310
324
324
321
321
380
380
COMPRESSORS
Quantity
Scroll
1
REFRIGERANT (R-410A)
Quantity (lb.)
7.0
8.9
8.9
9.3
9.3
9.5
9.5
REFRIGERANT METERING DEVICE
Orifice Indoor (in.)
AccuRater™ Piston
0.061
0.061
0.061
0.067
0.067
0.073
0.073
REFRIGERANT METERING DEVICE
Orifice Outdoor (in.)
AccuRater™ Piston
0.032 (2)
0.040 (2)
0.040 (2)
0.040 (2)
0.040 (2)
0.038 (2)
0.038 (2)
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
2...17
8.5
2...17
10.3
2...17
10.3
2...17
10.3
2...17
10.3
2...17
13.5
2...17
13.5
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
2350
22
1/8 (825)
2350
22
1/8 (825)
2350
22
1/8 (825)
2500
22
1/4 (1100)
2500
22
1/4 (1100)
2350
22
1/8 (825)
2350
22
1/8 (825)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...15
3.7
3...15
3.7
3...15
3.7
4...15
3.7
4...15
3.7
3...15
4.7
3...15
4.7
INDOOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (HP)
800
10 X 10
1/2
1000
10 X 10
1/2
1000
10 X 10
1/2
1200
11 X 10
3/4
1200
11 X 10
3/4
1400
11 X 10
3/4
1400
11 X 10
3/4
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas
Burner Orifice No. (Qty...Drill Size)
Propane Gas
2...44
2...50
2...44
2...50
2...38
2...46
2...38
2...46
3...38
3...46
2...38
2...46
3...38
3...46
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
610 ± 15
420 ± 25
LOSS-OF-CHARGE/LOW-
PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto)
20 ± 5
45 ± 10
RETURN-AIR FILTERS (in.)
Throwaway
20 X 20 X 1
20 X 20 X 1
20 X 20 X 1
20 X 24 X 1
20 X 24 X 1
24 X 30 X 1
24 X 30 X 1
* Based on altitude of 0 to 2000 ft.
15