15
InRoom Precision AC Tech Data Manual
InRoom Condensers - 50 Hz
* Condenser connections may not represent actual line sizing.
InRoom Remote Outdoor Condenser Data, 97°F ambient, 120°F condensation - R407C
InRoom Cabinet Size
1
2
3
4
5
Condenser Model (Qty) ACCD76002
ACCD76003
ACCD76002 (2) ACCD76003 (2)
ACCD76011(2)
Voltage
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
Number of Fans
2
2
3
3
3
Airflow m
3
/h (cfm)
13600 (8024)
13000 (7670) 13600 (8024) each 13000 (7670) each 16800 (9912) each
Motor kW (HP) - 
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
3 x 0.69
(3 x 0.92)
Refrigerant Connections*
Hot Gas Line - in
7/8 OD
7/8 OD
7/8 OD
1 3/8 OD
7/8 OD
Liquid Line - in 
7/8 OD
7/8 OD
7/8 OD
7/8 OD
7/8 OD
Weight - kg (lb)
72 (158)
81 (178)
2 x 72 (2 x 158)
2 x 81 (2 x 178)
2 x 144 (2 x 317)
InRoom Remote Outdoor Condenser Data, 115°F ambient, 131°F condensation - R407C
Condenser Model (Qty) ACCD76003
ACCD76011
ACCD76001 (2) ACCD76011 (2)
ACCD76019(2)
Voltage
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
Number of Fans
2
2
3
3
3
Airflow m
3
/h (cfm)
13000 (7670)
16800 (9912)
13000 (7670) each 16800 (9912) each 24000 (14160) each
Motor kW (HP) - 
2 x 0.69
(2 x 0.92)
3 x 0.69
(3 x 0.92)
2 x 0.69
(2 x 0.92)
2 x 0.69
(2 x 0.92)
3 x 0.62
(3 x 0.83)
Refrigerant Connections*
Hot Gas Line - in
7/8 OD
7/8 OD
7/8 OD
7/8 OD
1 3/8 OD
Liquid Line - in 
7/8 OD
7/8 OD
7/8 OD
7/8 OD
7/8 OD
Weight - kg (lb)
81 (178)
144 (317)
2 x 81 (2 x 178)
2 x 144 (2 x 317)
2 x 200 (2 x 440)
na
285
6
a