APC ACPCW40-150 User Manual

Page of 92
43
InRoom Precision AC Tech Data Manual
60Hz InRoom Electrical Specifications
Air Cooled (DX) and Fluid Cooled (Glycol) Electrical Data
With Reheat and 
Humidification
Without Reheat and 
Humidification
Compressor 
Data
Model 
Size
Airflow 
Pattern
Cooling System
Voltage 
(3ph/60Hz)
MCA
MOP
Power 
(kW)
MCA
MOP
Power 
(kW)
LRA
RLA
211
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230
67.3
70
20.6
33.3
50
10.6
137
19.3
460-480
34.5
35
21.0
15.6
20
9.9
62
9.1
575-600
30.2
35
29.3
15.2
20
11.3
62
9.1
PGEXXX
208-230
84.3
90
25.7
33.3
50
10.6
137
19.3
460-480
43.8
50
26.6
15.6
20
9.9
62
9.1
575-600
37.7
40
39.3
15.2
20
11.3
62
9.1
311
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230
100.3
125
30.4
49.3
80
15.3
195
32.1
460-480
53.0
60
32.0
24.7
40
15.3
95
16.4
575-600
42.2
45
32.3
19.9
30
14.3
95
16.4
PGEXXX
208-230
109.5
125
30.4
49.3
80
15.3
195
32.1
460-480
57.2
60
32.0
24.7
40
15.3
95
16.4
575-600
45.8
50
35.7
23.3
35
17.7
95
16.4
452
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230
116.0     
125
37.3
65.0
80
22.2   
156
20.7
460-480
59.2
60
37.8
30.9
40
21.0
75
10.0
575-600
42.5
45
36
29.3
35
24.7
75
10.0
PGEXXX
208-230
141.6
150
44.9
65.0
80
22.2
156
20.7
460-480
73.4
80
46.2
30.9
40
21.0
75
10.0
575-600
53.7
60
43.5
29.3
35
24.7
75
10.0
612
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230
167.3
175
53.3
90.6
100
30.6
195
32.1
460-480
87.8
90
55.7
45.3
60
30.5
95
16.4
575-600
57.1
60
44.7
35.3
45
27.1
95
16.4
PGEXXX
208-230
176.5
200
56.7
99.8
125
34.0
195
32.1
460-480
92.0
100
58.8
49.5
60
33.6
95
16.4
575-600
60.5
70
48.1
38.7
50
30.5
95
16.4
862
Up/
Down
PAXXX
PGXXX
PACWXXX
PGCWXXX
208-230
210.2
225
67.8
133.6
175
45.1
245
47.1
460-480
104.8
125
67.3
62.3
80
42.1
125
22.1
575-600
65.4
70
51.9
47.5
60
38.1
125
22.1
Note: Above data is based on maximum operating conditions
Installation must comply with all local and/or national electrical codes.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
LRA - Compressor Locked Rotor Amps
RLA - Compressor Rated Load Amps