APC ACPCW40-150 User Manual

Page of 92
InRoom Precision AC Tech Data Manual
62
50Hz InRoom Electrical Specifications 
Air Cooled (DX) and Fluid Cooled (Glycol) Electrical Data
Chilled Water (CW) Electrical Data
With Reheat 
and 
Humidification
Without 
Reheat and 
Humidification
Compressor Data
Model 
Size
Airflow 
Pattern
Cooling System
Voltage 
(3ph/
50Hz)
FLA
FLA
LRA
RLA
211
U/D
A/G/ACW/
GCW
400
32
14.7
75
10.0
GE
40.9
14.7
75
10.0
311
U/D
A/G/ACW/
GCW
400
48.2
22.0
114
17.3
GE
52.9
26.7
114
17.3
452
U/D
A/G/ACW/
GCW
400
59.6 33.4
100
12.0
GE
72.6
33.4
100
12.0
612
U/D
A/G/ACW/
GCW
400
83.2
44.0
114
17.3
GE
87.9
48.7
114
17.3
862
U/D
A/G/ACW/
GCW
400
102.3
63.1
135
24.5
With Reheat 
and 
Humidification
Without 
Reheat and 
Humidification
Model Size
Airflow 
Pattern
Cooling 
System
Voltage (3ph/
50Hz)
FLA
FLA
400
D
CW
400
29.5
3.5
400
U
CW
400
30.7
4.7
660
U/D
CW
400
43.1
8.2
900
U/D
CW
400
51.8
9.4
1100
U/D
CW
400
64.8
9.4
1500
U/D
CW
400
69.5
14.1