APC ACPCW40-150 User Manual

Page of 92
InRoom Precision AC Tech Data Manual
72
Upflow Chilled Water Cooling Units 
On upflow cooling units the supply and return pipes and power cables can be introduced from either the 
left or right side through openings in the side wall. The actual connection points are on the right side.
Dimensions are in mm (in).
Note: The 70 mm (2 3/4 in) pipe size on models CPW1100 and CPW1500 is decreased to 64 mm 
(2 1/2 in) diameter after the screw connection for the external pipe connection.
Model
PCW400
PCW660
PCW900
PCW1100
PCW1500
In/Out
Pipe Size
35 mm 
(1 3/8 in)
42 mm 
(1 5/8 in)
54 mm  
 (2 1/8 in)
70 mm 
(2 3/4 in)
70 mm 
(2 3/4 in)
Left Side 
Openings Used
L1, L2, L3, L4, 
L5, L6
L1, L2, L3, L4, 
L5, L6
L1, L2, L3, L4, 
L5, L6
L1, L2, L3, L4, 
L5, L6
L1, L2, L3, L4, 
L5, L6
Right Side 
Openings Used
R1, R2, R3, R4, 
R5, R6
R3, R4, R5, R6 R1, R2, R3, R4, 
R5, R6
R1, R2, R3, R4 
R1, R2, R3, R4 
60
210 (8.3)
405 (15.9)
525 (20.7)
680 (26.8)
230 (9.1)
110 (4.3)
680 (26.8)
485 (19.1)
365 (14.4)
210 (8.3)
n
a
28
49
a
L7
0
110 (4.3)
230 (9.1)
0
L5 L3
L1
L8
L6 L4
L2
60
R1
R3 R5
R7
R2
R4 R6
R8
Left Side Connections
Right Side Connections