APC ACPDX21-86 User Manual

Page of 92
InRoom Precision AC Tech Data Manual
44
Chilled Water (CW) Electrical Data
With Reheat and 
Humidification
Without Reheat and 
Humidification
Model 
Size
Airflow 
Pattern
Cooling System
Voltage 
(3ph/60Hz)
MCA
MOP
Power 
(kW)
MCA
MOP
Power 
(kW)
400
Down
PCWXXX
208-230
59.0
60
18.8
9.9
15
3.1
460-480
32.7
35
20.8
4.4
15
2.8
575-600
28.7
30
22.9
6.2
15
4.9
400
Up
PCWXXX
208-230
60.6
70
19.3
11.5
20
3.7
460-480
33.5
35
21.4
5.3
15
3.3
575-600
28.7
30
22.9
6.2
15
4.9
660
Up/Down
PCWXXX
208-230
91.6
100
29.2
19.8
25
6.3
460-480
46.5
50
29.6
8.9
15
5.7
575-600
39.7
40
31.7
9.7
15
7.7
900
Up/Down
PCWXXX
208-230
109.4
125
34.9
23.0
25
7.3
460-480
56.4
60
35.9
10.5
15
6.7
575-600
47
50
37.6
10.4
15
8.3
1100
Up/Down
PCWXXX
208-230
135.0
150
43.0
23.0
25
7.3
460-480
70.6
80
45.0
10.5
15
6.7
575-600
47
50
37.6
10.4
15
8.3
1500
Up/Down
PCWXXX
208-230
146.5
150
46.7
34.5
35
11.0
460-480
75.9
80
48.4
15.8
20
10.0
575-600
62.5
70
50
14.7
20
11.7
Note: Above data is based on maximum operating conditions
Installation must comply with all local and/or national electrical codes.
MCA - Minimum Circuit Ampacity
MOP - Maximum Overcurrent Protection
LRA - Compressor Locked Rotor Amps
RLA - Compressor Rated Load Amps