APC ACPA4000 User Manual

Page of 52
9
NetworkAIR ACPA4000
Install the adapter in a drop ceiling
Use the ceiling adapter to provide an intake and exhaust outlet for the condenser.
Note: Allow at least 305 mm (12 in) of open space above the ceiling adapter opening so 
exhaust air is not blocked.
1. Determine a location to install the ceiling adapter.
2. Remove the ceiling tile in the chosen location and 
save it for a future step.
3. Place the ceiling adapter into the ceiling tile grid.
4. Secure the ceiling adapter to the building structural 
support (not the drop ceiling), using 10-gauge (minimum) steel wire.
5. When using 2 x 4 ft ceiling tiles, insert a cross 
member (not provided) for added support.