APC ACPA4000 User Manual

Page of 52
NetworkAIR ACPA4000
34
Programmable settings
Product data
• Device name— Your device name
• Product location—Location of the 
equipment
• Product contact—Name of contact
Status
Menu Item
Setting Variable
Run hours
• Alarm: 1000–9000 hrs.
• Clear Total (Reset to Zero)—Yes/No
Contact I/O
• Inputs
– Input—Mains fail/Remote 
stop
– Name—Enter name
– Normal—Open/Closed
– Status—Open/Closed
• User inputs 
• Input—1 of 3/3 of 3
• Name—Enter equipment name 
(14-character limit)
• Normal—Open/Closed
• Status—Open/Closed
Control Environment
Menu Item
Setting Variable
Mode
• System off/Cool/Vent only
Blower
• High/Low
Setpoint
• 16 to 32°C (60° to 90°F)
Deadband
• 0.6° to 1.7°C (1° to3°F)
Setup
Menu Item
Setting Variable