APC ACPSC3000 User Manual

Page of 32
InRoom SC 50 Hz User Guide
12
Drain Kit Installation
The InRoom SC utilizes evaporative technology, which eliminates the need for a condensate tank. To 
manage any excess condensation, a drain pan is located in the bottom of the unit. When the drain pan is 
full, a light will flash on the display and an alarm will sound to alert you. The cooling unit will 
automatically shut down. To avoid a shut down, install the drain kit and route the hose to a drain.
See “Inventory” on page 6 for a description of the contents of the drain hose kit.
1. Attach the plastic hose clip to 
the back of the cooling unit with 
the screw provided.
2. Remove the drain cap from the 
back of the cooling unit.
3. Attach the drain hose to the 
drain pipe with the hose clamp 
included in the kit.
4. Remove the plug from the end 
of the hose to empty the drain 
pan and then replace the plug if 
the hose is not permanently 
installed to a drain.
5. With the plug installed, press 
the drain hose into the hose clip 
to keep it out of the way when 
not in use.
Continuous draining 
 
Note: Continuous drainage is recommended when the unit is used in DRY mode.
 
 
Caution: Condensate draining is done by gravity. Do not run a drain hose to a drain that is 
located above the drain port of the cooling unit. 
 
MODE
InRoom 
SC
TEMP
na3393a